10 field network status leds, 1 devicenet, 2 cc-link – IAI America MSCON User Manual
Page 235

3.10 Field network status LEDs
227
3.10 Field network status LEDs
The communication status of the field network can be checked.
3.10.1 DeviceNet
NS
MS
3.10.2 CC-Link
ERR
RUN
{
: Illuminating, × : OFF, : Flashing
Name
Lamp
status
Color
Description
{
Online (normally)
Green
Online (Even though the network
is established normally, it is not
identified as MSCON by the
master)
{
An error occurs.
Orange No response returned from
another slave.
NS
(Illuminated
by turns)
Green /
Orange In self-checking process.
{
Communication in normal
condition
Green
Parameter setting error
{
Hardware breakdown
Orange Light malfunction
MS
(Illuminated
by turns)
Green /
Orange In self-checking process.
Field
Network
Connector
Field
Network
Status
LED
{
: Illuminating, × : OFF, : Flashing
Name
Lamp
status
Color
Description
{
An error occurs. (CRC error,
station No. setting error, baud
rate setting error)
Orange
Station number or baud rate
changed after the power-on
ERR
×
–
Normal
RUN
{
Green Communication in normal
condition
Field
Network
Connector