Chapter 7 Parameter
264
[26] Auto servo motor OFF delay time 1, 2, 3 (Parameter No.36, No.37, No.38)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
36 Auto Servo-motor OFF Delay
Time 1
ASO1
sec
0 to 9999
0
37 Auto Servo-motor OFF Delay
Time 2
ASO2
sec
0 to 9999
0
38 Auto Servo-motor OFF Delay
Time 3
ASO3
sec
0 to 9999
0
Set the duration before the servo turns OFF after positioning process is complete when the
power saving function is used.
[Refer to Chapter 5 Power-saving Function.]
[27] Position complete signal output method (Parameter No.39)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
39 Position Complete Signal Output
Method
FPIO
-
0: PEND
1: INP
0
This is the parameter to select the type of the positioning complete signals to be used.
It is available except for when PIO Pattern = 5 (Solenoid Valve Type 2 [3-point type]) is
selected.
There are 2 types of positioning complete signals and the output condition would differ
depending on whether the servo is ON after the positioning is complete or the servo is OFF.
Setting
Signal Type
During Servo ON
(positioning complete)
During Servo OFF
0
PEND
It will not turn OFF even if the
current position is out of the range
of the positioning width.
Turns OFF in any
case
1
INP
Turns ON when the current position is in the positioning
width, and OFF when out of it.
Complete position No. outputs PM1 to PM** and current position No. outputs PE0 to PE6 are
issued in the similar way.
[28] Home return input disable (Parameter No.40)
No.
Name
Symbol
Unit
Input Range
Default factory
setting
40 Home-return Input Disable
FPIO
-
0: Enabled
1: Disable
0
This parameter defines whether the home return input signal is disabled or enabled.
Normally this parameter need not be changed.
Set Value
Description
0
Enabled (Use)
1
Disable (Does not use)