3.4 Fieldbus
Type
Address Map
107
(3) I/O signal assignment
(ON = Applicable bit is “1”, OFF = Applicable bit is “0”)
Signal Type
Bit
Symbol
Contents
Details
Target Position
32
Bit
data
–
32-bit signed integer indicating the current position
Unit: 0.01mm
Available range for Setting: -999999 to 999999
Set the target position with the value from the home
position.
(Example) If +25.40mm, input 000009EC
H
(2540 in
decimal system).
(Note) Input the negative value using a compliment of
2.
3.7 (28)
Positioning Width
32
Bit
data
–
32-bit integer
Unit: 0.01mm
Available range for Setting: 0 to 999999
(Example) If +25.40mm, input 000009EC
H
(2540 in
decimal system).
This register value has two meanings depending on
the operation type.
1) Positioning operation
Range for positioning complete against the target
position
2) Pressing operation
Pressing width (Pressing operation distance)
A pressing operation is performed when PUSH
Signal in the control signals is ON.
3.7 (28)
Command Speed
16
Bit
data
–
16-bit integer
Unit: 1.0mm/sec or 0.1mm/sec (It is set to 1.0mm/sec
in the initial setting.)
A change of the unit is to be conducted on Gateway
Parameter Setting Tool.
Available range for Setting: 1 to 65535
Specify the speed at which to move the actuator.
(Example) If 254.0mm/sec (1.0mm/s unit), input 09EC
H
(2540 in decimal system).
It may cause an alarm or a malfunction if executing a
movement command with 0 or a value more than the
maximum speed of the actuator.
3.7 (28)
Acceleration/Deceleration
16
Bit
data
–
16-bit integer
Unit: 0.01G
Available range for Setting: 1 to 300
Specify the speed at which to move the actuator. The
acceleration and deceleration will be the same value.
(Example) If 0.30G, input 001E
H
(30 in decimal
system).
It may cause an alarm or a malfunction if executing a
movement command with 0 or a value exceeding the
maximum acceleration/deceleration of the actuator.
3.7 (28)
P
LC
O
ut
pu
t
Pressing Current Limit
16
Bit
data
–
16-bit integer
Unit :
%
Available range for Setting: 0 to 100
Indicate the current value for pressing operation.
(Example) If “50%”, input “007F
H
”.
The pressing range available for indication differs
depending on the actuator (Refer to the catalog or
instruction manual for the actuator). It may cause an
alarm or a malfunction if executing a movement
command with a value more than the maximum
pressing current.
3.7 (28)