As - analog scaling, Command details, Parameter details – Applied Motion RS-232 User Manual
Page 33: Examples

33
920-0002 Rev. I
2/2013
Host Command Reference
AS - Analog Scaling
Compatibility: All stepper drives and SV servo drives
Affects:
Analog input
See also:
CM command
Sets or requests the analog input scaling setting. This is a code that determines what type of analog input scaling
is desired. The codes for selecting the various settings are in the Details table below.
Command Details:
Structure
AS{Parameter #1}
Type
BUFFERED
Usage
READ/WRITE
Non-Volatile
YES
Register Access
None
Parameter Details:
Parameter #1
Code
- units
integer number
- range
0 = single-ended +/- 10 volts
1 = single-ended 0 - 10 volts
2 = single-ended +/- 5 volts
3 = single-ended 0 - 5 volts
4 = differential +/- 10 volts
5 = differential 0 - 10 volts
6 = differential +/- 5 volts
7 = differential 0 - 5 volts
Examples:
Command
Drive sends
Notes
AS2
-
Analog input scaling set to single-ended +/- 5 volts
AS AS=2