KEYENCE DV-90 User Manual
Page 236
9-36
E DV-90-IM
9
PLC Link
Check that the values to be written in +01, +02, and +03 are within the range supported by the DV-
90 and the PLC. (
Refer to 9-3.)
Note that the range of values written in +01, +02, and +03 +50 is used, and therefore should be sup-
ported by the DV-90 and the PLC.
Check the connections, settings, and range of DMs, and perform the steps again starting from Step
2.
➆When PLC link communication is correctly established but the data is not written correctly, check
the following points.
• Write “1” in the DM (Communication Start Notice Flag) of the “DM Address” set in the DV-90
+00, and check whether or not communication has started. (
Refer to 9-4.)
• Communication will not start unless “1” is written in “Communication Start Notice Flag”.
• Indirectly specify the head address in which the read data of the code reader is written as the DMs
(Data Write Head Address) of the “DM Address” +01, +02, and +03.
(
Refer to page 9-7.) Check that the correct address is specified as the “data write head
address”.
• When the DM “Data Write Process Notice Area” of “DM Address” +08 is set to “1 (Sequence
processing)”, check whether or not the DM “Data Write Enabled Notice Flag” of the “DM
Address” +10 is set to “0 (Data Write Disabled)”.(
Refer to 9-10.)
In sequence processing, the read data is not written unless “Data Write Enabled Notice Flag” of
+10 DM is set to “1 (Data Write Enabled)”.
➇When the screen to the right appears when using Ver-
ify Active, the selected active record number is not in
the range between 1 and 900. Be sure to set the cor-
rect value. (
Refer to page 9-11)
Note
• If performing communication as a test, set the “DM Address” to “0000”, and write “100” in
DM0001, “200” in DM0002, and “300” in DM0003. Then, check that the read data is writ-
ten in DM100, DM200, and DM300.
• “PLC Link Error Invalid DM” that occurs at step 2 occurs when the values to write in +01,
+02, and +03 are not in the range between 1 and 9999. Note that the range supported by
the PLC is not considered.
Note
• Be sure to restart the PLC after you send settings to it.
P L C L i n k E r r o r
A c t i v e N o [ E S C ]