beautypg.com

KEYENCE DV-90 User Manual

Page 231

background image

9-31

9

E DV-90-IM

PLC Link

9-5 Settings

„ C500-LK201-V1 , C500-LK203

* In the C500-LK201-V, the data length, parity, and stop bit are fixed to 7, even, and 2, respectively.

„ CV500, CV1000, CVM1

(Switch)

(DIP switch)

(System setting)

Link unit

C500-LK201-V1 C500-LK203

5-V supply selection

OFF

Input/output port selection

RS-232C

Synchronization selection

Internal

CTS selection

0 V

Unit number

0

Parity

Even

Transmission code

Data length: 7 bits
Stop bit: 2 bits

Transmission speed

*

9600 bits/s

1:1/1: N Handshake

1: N Handshake

Level setting

Valid for level 1, 2, and 3

Link unit

CPU internal port

CV500-LK201

Unit number (Port 2)

00

RS-232C/RS-422A selection

RS-232C

Communication path selection (port 2)

RS-232C

5 V output setting (port 2)

No 5-V supply

Communication condition setting

Communicates in the PC system
value (SW4-OFF)

Communicates in the PC system
value (SW1-OFF)

CTS selection

CTS always ON (SW2-ON, SW3-
ON)

Loopback communication test

Normal operation (SW5-OFF,
SW6-OFF)

Unit number

00

Transmission speed

9600 bits/s

Stopbit length

2 bits

Parity

Even

Data length

7 bits

Xon/Xoff control

Not performed

Communication method

Full duplex