Installing and starting up the "CrossCutter" prepared solution
Prepared Solution Servo PLC / ECSxA 1.1 EN
3-102
The signal sources for the data words (designated Word 0, Word 1, Word 2 and Word 3) are
dependent on the operating mode in C4000/000:
Signal source
Word 0
Word 1
Word 2
Word 3
C4000/000 = 0
C0135/000
C4137/000
C4135/000
C4000/000 = 1
CAN1_wDctrlCtrl CAN1_nInW1_a CAN1_nInW2_a CAN1_nInW3_a
C4000/000 = 2
CAN2_nInW1_a CAN2_nInW2_a CAN2_nInW3_a CAN2_nInW4_a
C4000/000 = 3
CAN3_nInW1_a CAN3_nInW2_a CAN3_nInW3_a CAN3_nInW4_a
C4000/000 = 4
AIF1_wDctrlCtrl AIF1_nInW1_a AIF1_nInW2_a AIF1_nInW3_a
C4000/000 = 5
AIF2_nInW1_a AIF2_nInW2_a AIF2_nInW3_a AIF2_nInW4_a
C4000/000 = 6
AIF3_nInW1_a AIF3_nInW2_a AIF3_nInW3_a AIF3_nInW4_a
The illustration of the 32-bit application control word (Word 3 and Word 4) on the previous page
shows the factory-set default configuration. Users can also adapt the configuration of the
application control word in accordance with their individual needs by setting the values of codes
C4010/001 to C4010/032 accordingly.
An example of how the GDC parameterisation software can be used to reconfigure the
application control word bit by bit appears below:
You will find the code in the complete code list or in the menu (Short Setup Control/Status Interface
Control Interface):
Select code C4010/00x which is assigned to the function to be configured.
Example: The control signal for manual jog in a positive direction is defined in code C4010/004:
Start
Step 1