Other parameters – IAI America XSEL-QX User Manual
Page 488

464
Appendix
7. Other
Parameters
No. Parameter
name
Default value
(Reference)
Input range
Unit
Remarks
1 Auto-start
program
number
0
0 ~ 64
(Invalid if “0” is set)
2
I/O processing program
number at
operation/program abort
0
0 ~ 64
The start trigger is determined from the “I/O processing
program start type at operation/program abort.” (Note:
This program will be started before confirming an abort
of other programs.)
(Invalid if “0” is set) * If the setting is valid, the number of
user program tasks that can be used will decrease by 1.
3
I/O processing program
number at all operation
pause
0
0 ~ 64
This program will be started when an all-operation-
pause command is issued due to an all-operation-pause
factor. (Only when a program is running) (Invalid if “0” is
set) * If the setting is valid, the number of user program
tasks that can be used will decrease by 1.
4
Program abort type at
error
0
0 ~ 5
0: Cancel only the program in which an error of
operation-cancellation level or higher has generated.
(If the error requires the drive source to be cut off,
servo OFF or all-axis servo OFF, all programs other
than the “I/O processing program at
operation/program abort” will be cancelled.)
1: Cancel all programs other than the “I/O processing
program at operation/program abort” when an error
of operation-cancellation level or higher has
generated.
5
I/O processing program
start type at
operation/program abort
0
0 ~ 5
0: When all-operation-cancellation factor has generated
(Only when a program is running)
1: When all-operation-cancellation factor has generated
(Always)
2: All-operation-cancellation factor + Error of operation-
cancellation level or higher (“Other parameter No. 4
= 0” is considered) (Only when a program is running)
3: All-operation-cancellation factor + Error of operation-
cancellation level or higher (“Other parameter No. 4
= 0” is considered) (Always)
6 PC/TP
reconnection
delay at software reset
14000
1 ~ 99999
msec
* The setting will become effective after the controller,
PC software or TP is restarted.
7~8 (For
extension)
0
9
For future extension
(Change prohibited)
0
0 ~ 9
10 Emergency-stop
recovery type
0
0 ~ 4
0: Abort operations/programs
1: Recovery after reset
2: Operation continued (Only during automatic
operation.
* Operation commands from the PC software/TP will
be aborted from the PC software/TP side.)
3: Abort operations/programs (Software reset when the
emergency stop is reset. The home-return
completion status of incremental-encoder axes will
be reset (EG approximation swap)).
4: Abort operations/programs (Error reset (only with an
error of operation-cancellation level or lower) and
auto-start program start (only if AUTO mode AND I/O
parameter No. 33 = 1 AND I/O parameter No. 44
z 1
AND all-operation-cancellation factor is not present)
when the emergency stop is reset). There must be a
minimum interval of 1 second after an emergency
stop is actuated before it is reset. The home-return
completion status of incremental-encoder axes will
be retained.)
11
Enable switch (deadman
switch/enable switch)
recovery type
0
0 ~ 2
0: Abort operations/programs
1: Recovery after reset
2: Operation continued (Only during automatic
operation. * Operation commands from the PC
software/TP will be aborted from the PC software/TP
side.)
PC: PC
software
TP: Teaching
pendant