Echelon OpenLNS Commissioning Tool User Manual
Page 328

312
Creating and Using Custom OpenLNS CT Shapes and Stencils
NewAdvPropCap
Specifies handling of the advanced properties dialog in the new
device wizard.
• A value of 0 specifies that the advanced properties dialog is
not to be displayed.
• A value of 1 indicates that the advanced properties dialog is
to be displayed, but cannot be modified.
• A value of 2 indicates that the advanced properties dialog is
displayed and changes can be made.
• The default value is 0 (the advanced properties dialog is not
displayed).
NewPropCap
Specifies handling of the basic properties dialog in the new device
wizard.
• A value of 0 specifies that the basic properties dialog is not to
be displayed.
• A value of 1 indicates that the basic properties dialog is to be
displayed, but cannot be modified.
• A value of 2 indicates that the basic properties dialog is
displayed and changes can be made.
• The default value is 2 (the basic properties dialog is displayed
and changes are allowed).
NonGrpRcvTimer
Specifies the default non-group receive timer; a value of -1
indicates that the OpenLNS Server default value will be used.
Otherwise, the value is encoded as follows:
Encoded
Value
Seconds
0
0.016
1
0.024
2
0.032
3
0.048
4
0.064
5
0.096
6
0.128
7
0.192
8
0.256
9
0.384
10 0.512
11 0.768
12 1.024
13 1.536
14 2.048
15 3.072
NxeName
Specifies the file name or full path of the application file. If it is
not specified here, the OpenLNS CT user will be prompted for an
application file when a request is made to load the application
image.
ObjStateStyle