Chapter 4 Setup Page

RMC Module • Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[`C;hy]
[ C.hy]

Control Loop (1 to 4)

Cool Hysteresis **

Set the control switch-

ing hysteresis for on-off

control. This deter-

mines how far into the

“on” region the process

value needs to move

before the output turns

on.

0.001 to 9,999.000°F or units

0.001 to 5,555.000°C

3.0°F or

units

2.0°C

2242

[offset 70]

0x97

(151)

1 to 4

0xC (12)

68

8013

float

RWES

[``ti]
[ ti]

Control Loop (1 to 4)

Time Integral **

Set the PID integral for

the outputs.

0 to 9,999 seconds per repeat

180 sec-

onds per

repeat

2234

[offset 70]

0x97

(151)

1 to 4

8

69

8006

float

RWES

[``td]
[ td]

Control Loop (1 to 4)

Time Derivative **

Set the PID derivative

time for the outputs.

0 to 9,999 seconds

0

seconds

2236

[offset 70]

0x97

(151)

1 to 4

9

70

8007

float

RWES

[``dB]
[ db]

Control Loop (1 to 4)

Dead Band **

Set the offset to the

proportional band.

With a negative value,

both heating and cool-

ing outputs are active

when the process value

is near the set point.

A positive value keeps

heating and cooling

outputs from fighting

each other.

-1,000.0 to 1,000.0°F or units

-556 to 556°C

0.0

2238

[offset 70]

0x97

(151)

1 to 4

0xA (10)

71

8008

float

RWES

[t;tUn]
[t.tUn]

Control Loop (1 to 4)

TRU-TUNE+

®

Enable

Enable or disable the

TRU-TUNE+

®

adaptive

tuning feature.

[``no]

No (59)

[`YES}

Yes (106)

No

2250
[offset 70]

0x97 (151)

1 to 4

10 (16)

- - - -

8022

uint

RWES

[t;bnd]
[t.bnd]

Control Loop (1 to 4)

TRU-TUNE+

®

Band

Set the range, centered

on the set point, within

which TRU-TUNE+

®

will be in effect. Use this

function only if the con-

troller is unable to adap-

tive tune automatically.

0 to 100

0

2252
[offset 70]

0x97 (151)

1 to 4

0x11 (17)

- - - -

8034

uint

RWES

[`t;gn]
[ t.gn]

Control Loop (1 to 4)

TRU-TUNE+

®

Gain

Select the respon-

siveness of the TRU-

TUNE+

®

adaptive tun-

ing calculations. More

responsiveness may

increase overshoot.

1 to 6

3

2254
[offset 70]

0x97 (151)

1 to 4

0x12 (18)

- - - -

8035

uint
RWES

Note:

Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set