beautypg.com

Watlow EZ-ZONE RMC User Manual

Page 136

background image

Watlow EZ-ZONE

®

RMC Module

133

Chapter 5 Profiling Page

RMC Module •

Profile Page

Display

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data Type

& Read/

Write

[``SC]
[ SC]

Step (1 to 250)

Subroutine Count

If step type is Subrou-

tine, specify number

of times to execute

subroutine steps.

1 to 9,999

1

5508

[offset 100]

0x79

(121)

1 to (250)

0x23 (35)

- - - -

21035

uint

RWE

[~~JS]
[ JS]

Step (1 to 250)

Jump Step

If step type is Jump

Loop, select a step to

jump next.

Step-1 (Minimum of 1)

1

5462

[offset 100]

0x79

(121)

1 to (250)

0xC (12)

- - - -

21012

uint

RWE

[~~JC]
[ JC]

Step (1 to 250)

Jump Count

If step type is Jump

Loop, set the number

of jumps. A value of

0 creates an infinite

loop. Loops can be

nested four deep.

0 to 9,999

1

5464

[offset 100]

0x79

(121)

1 to (250)

0xD (13)

- - - -

21013

uint

RWE

[~End]
[ End]

Step (1 to 250)

End Type

If step type is End, se-

lect what the control-

ler will do when this

profile ends.

[`oFF]

Control Mode set

to Off (62)

[Hold]

Hold last closed-

loop set point in the pro-

file (47)*

[USEr]

User, reverts to

previous set point (100)

* End Hold does not affect

the control mode, only

the closed loop set point.

The profile will return to

the control mode prior to

starting the profile.

User

5466

[offset 100]

0x79

(121)

1 to (250)

0xE (14)

- - - -

21014

uint

RWE

[Ent1]
[Ent1]

Step (1 to 250)

Event 1

Select whether output

programmed as Pro-

file Event Out A is on,

unchanged or off dur-

ing this step.

[`oFF]

Off (62)

[Ucgd]

Unchanged (1557)

[``on]

On (63)

Un-

changed

5452

[offset 100]

0x79

(121)

1 to (250)

7

- - - -

21007

uint

RWE

[Ent2]
[Ent2]

Step (1 to 250)

Event 2

Select whether output

programmed as Pro-

file Event Out B is on,

unchanged or off dur-

ing this step.

[`oFF]

Off (62)

[Ucgd]

Unchanged (1557)

[``on]

On (63)

Un-

changed

5454

[offset 100]

0x79

(121)

1 to (250)

8

- - - -

21008

uint

RWE

[Ent3]
[Ent3]

Step (1 to 250)

Event 3

Select whether output

programmed as Pro-

file Event Out C is on,

unchanged or off dur-

ing this step.

[`oFF]

Off (62)

[Ucgd]

Unchanged (1557)

[``on]

On (63)

Un-

changed

5470

[offset 100]

0x79

(121)

1 to (250)

0x10 (16)

- - - -

21016

uint

RWE

Note: Some values will be rounded off to fit in the four-character display . Full values

can be read with other interfaces .
If there is only one instance of a menu, no submenus will appear .

R: Read

W: Write

E: EEPROM

S: User Set