Chapter 8 Appendix
Indication
Description
Possible Cause(s)
Corrective Action
Remote User Inter-
face (RUI) menus
inaccessible
Unable to access [`SEt],
[OPEr]
, [FCty] or [ProF]
menus or particular prompts
in Home Page
• Security set to incorrect level
• Check [`loC] settings in Factory Page
• Enter appropriate password in [UloC]
setting in Factory Page
• Digital input set to lockout keypad
• Change state of digital input
• Custom parameters incorrect
• Change custom parameters in Factory
Page
RUI value to low
[ual;l]
Value to low to be displayed
in 4 digit LED display
<-1999
• Incorrect setup
• Check scaling of source data
RUI value to high
[ual;h]
Value to high to be displayed
in 4 digit LED display
>9999
• Incorrect setup
• Check scaling of source data
Detection of and Rules Around Abnormal Sensor Conditions
Inputs
Detection of Abnormal Conditions
Thermocouple
Shorted
No direct detection, Open loop firmware detection.
Open
Yes, Parasitic pull-up
Reversed
Yes, firmware detection
Current Source
Shorted
Range limiting only
Open
Range limiting only
Reversed
Range limiting only
Voltage Source
Open
Range limiting only
Shorted
Range limiting only
Reversed
Range limiting only
RTD
S1 open
Yes, pulled up.
S2 open
Not implemented.
S3 open
Yes, pulled up.
S1 short to S2 Yes, pulled up
S1 short to S3 Yes, pulled down to under range.
S2 shorted to S3 Not implemented, Possible, monitor S2 voltage.
S1 and S2 open Yes, pulled down to under range.
S1 and S3 open Yes, S1 pulled up.
S2 and S3 open Yes pulled up.
Thermistor
S1 open
Yes, pulled up to sensor over range.
S3 open
Yes, pulled up to sensor over range.
S1 short to S3 Yes, pulled down to sensor under range.
S1 and S3 open Yes, S1 pulled up to sensor over range.