Chapter 1 Overview

A Conceptual View of the RMC Module

The flexibility of the RMC software and hardware al-

lows a large range of configurations. Acquiring a bet-

ter understanding of the controller’s overall function-

ality and capabilities while at the same time plan-

ning out how the controller can be used will deliver

maximum effectiveness in your application.

The RMC can be connected at the system level to

as many as 17 modules, one of which can be an Ac-

cess module and the others (16 maximum) can be any

combination of available modules. The user will de-

fine each address via the button on the face of each

module. Each installed RMC module must have a

unique Standard Bus address ranging from 1-9, A-F,

where the factory defaults for each is Standard Bus

address 1.

Getting Started Quickly

The RMC (Controller) can be ordered with up to

four PID loops with default loop configurations (all

loops) out of the box as follows:

• Analog Input functions set to thermocouple, type

J

• Control loops 1-4 use Analog Inputs 1-4
• Heat algorithm set for PID, Cool set to off
• Outputs set to off
• Control mode set to Auto
• Set point set to 75 °F

To enable a loop for heat simply follow the steps be-

low:

1. Navigate to the Setup Page

2. Once on the Setup Page navigate to the Output

Menu and then the output of choice

3. Change the default setting of Off to Heat Power

4. Select the desired loop instance

EZ-ZONE RMC Default Configuration

Heat

Thermocouple Type J

Analog Input 1

PID

Controller

Heat

Slot A

Loop 1

Input Sensor

Output

Function

Input

Function

Output 1

Off

Note:

Zones can communicate with one another over the

backplane (local and split rail). Once the system is

configured and running, changing zone addresses

without careful deliberation may cause disruption in

operation.

Some of the user selectable ordering options are

listed below:
1. Class 2 or SELV (Safety Extra Low Voltage) equiv-

alent Power Supplies:

• 90-264 Vac to 24Vdc @ 31 watts

• 90-264 Vac to 24Vdc @ 60 watts

• 90-264 Vac to 24Vdc @ 91 watts

2. RMC Module can provide:

• 1 to 4 control loops, limits or CT inputs

• 1 to 9 inputs (various types)

• 1 to 12 outputs (various types)

• Modbus RTU communications

As can be seen above the RMC module is fully scal-

able with regards to power requirements, number of

loops, inputs, and outputs.

It is useful to think of the controller in three

parts: inputs, functions and outputs. Information

flows from an input to a function to an output when

the controller is properly configured. An RMC mod-

ule can carry out several functions at the same time,

e.g., PID control, monitoring for several different

alarm situations, monitoring and acting upon Digi-

tal Inputs and driving output devices such as heat-

ers, audible alarms, lights. Each process needs to

be thought out carefully and the controller’s inputs,

functions and outputs set up properly.

Functions

Outputs

Process

Alarm

High

PID

Heat

Power

Sequencing

Outputs

Silence

Alarms

Inputs

Functions

Functions use input signals to calculate a value. A

function may be as simple as reading a digital input

to set a state to true or false, or reading a tempera-

ture to set an alarm state to on or off. Alternatively,

if a failure with the primary sensing device should

occur, sensor backup could be utilized to avoid an un-

wanted shutdown.

To set up a function, one of the first things that

must be considered is the function source and in-

stance. For example, if the control is equipped with

Digital Inputs (source) and it was decided to use DI 9

(instance) it can then be associated with an Action to

reset an individual alarm or all alarms. To configure

as such, follow the steps below:

Setup Page (Digital I/O Menu)

1. Navigate to the Setup Page and then to the Digital

I/O menu.

2. Select the desired instance and set the direction to

input voltage or input dry contact.

Setup Page (Action Menu)

3. Navigate to the Setup Page and then the Action

menu.

4. Set the Action Function to Alarm
5. Select which alarm instance will be reset (0 equals

all)

6. Select the Source Function to Digital I/O
7. Select the Source Instance (step 2 above)
8. Select the Source Zone (0 equals the module being

configured).

9. Select the Active Level to execute the desired func-

tion.