Math menu – Watlow EZ-ZONE RMC User Manual
Page 109
Watlow EZ-ZONE
®
RMC Module
•
106
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[`Er;h]
[ Er.h]
Logic (1 to 4)
Error Handling
Use to select the output
value and error output
state of this function if it
receives an error signal
from one or more sources
and it cannot determine
the output value.
[``t;g]
True Good (1476)
[``t;b]
True Bad (1477)
[``F;g]
False Good (1478)
[``F;b]
False Bad (1479)
False Bad 3748
[offset 80]
0x7F (127)
1 to 4
0x23 (35)
- - - -
27035
uint
RWES
[MAt]
[`Set]
Math Menu
[``Fn]
[ Fn]
Math (1 to 8)
Function
Set the operator that
will be applied to the
sources.
[`oFF]
Off (62)
[`Aug]
Average (1367)
[`P;SC]
Process Scale (1371)
[`d;SC]
Deviation Scale (1372)
[``s;o]
Switch Over (1370)
[diFF]
Differential (1373)
[rAti]
Ratio (1374)
[`Add]
Add (1375)
[MUL]
Multiply (1376)
[A;diF]
Absolute Difference
(1377)
[Min]
Minimum (1378)
[MAH]
Maximum (1379)
[root]
Square Root (1380)
[hoLd]
Sample and Hold (1381)
[`alt]
Pressure to Altitude
(1649)
[dew]
Dewpoint (1650)
Off
2880
[offset 70]
0x7D
(125)
1 to 8
0x15 (21)
128
25021
uint
RWES
[SFn;A]
[SFn.A]
Math (1 to 8)
Source Function A
Set the type of function
that will be used for this
source.
[nonE]
None (61)
[``Ai]
Analog Input (142)
[CUrr]
Current (22)
[`C;Pr]
Cool Power, Control
Loop (161)
[`h;Pr]
Heat Power, Control
Loop (160)
[PWr]
Power, Control Loop (73)
[`Lnr]
Linearization (238)
[MAt]
Math (240)
[``Pu]
Process Value (241)
[`SP;C]
Set Point Closed, Con-
trol Loop (242)
[`SP;o]
Set Point Open, Control
Loop (243)
[`uAr]
Variable (245)
None
2840
[offset 70]
0x7D
(125)
1 to 8
1
- - - -
25001
uint
RWES
[`Si;A]
[ Si.A]
Math (1 to 8)
Source Instance A
Set the instance of the
function selected above.
1 to 250
1
2850
[offset 70]
0x7D
(125)
1 to 8
6
- - - -
25006
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set