Analog input menu – Watlow EZ-ZONE RMC User Manual

Page 66

background image

Watlow EZ-ZONE

®

RMC Module

63

Chapter 4 Setup Page

RMC Module • Setup Page

Dis-

play

Parameter Name

Description

Range

Default

Modbus

Relative

Address

CIP

Class

Instance

Attribute

hex (dec)

Profibus

Index

Parameter

ID

Data

Type

& Read/

Write

[``Ai]
[`Set]
Analog Input Menu

[`Sen]
[ SEn]

Analog Input (1 to 4)

Sensor Type

Set the analog sensor

type to match the device

wired to this input.

Note:

There is no open sensor

protection for process
inputs.

[`oFF]

Off (62)

[``tC]

Thermocouple (95)

[`mu]

Millivolts (56)

[uolT]

Volts dc (104)

[`MA]

Milliamps dc (112)

[r0;1H]

RTD 100 Ω (113)

[r1;0H]

RTD 1,000 Ω (114)

[`Pot]

Potentiometer 1 kΩ

(155)

[thEr]

Thermistor (229)

Thermo-

couple or

Thermis-

tor

368
[offset 90]

0x68 (104)

1 to 4

5

3

4005

uint
RWES

[`Lin]
[ Lin]

Analog Input (1 to 4)

TC Linearization

Set the linearization to

match the thermocouple

wired to this input.

[```b]

B (11)

[```H]

K (48)

[```C]

C (15)

[```n]

N (58)

[```d]

D (23)

[```r]

R (80)

[```E]

E (26)

[```S]

S (84)

[```F]

F (30)

[```t]

T (93)

[```J]

J (46)

J

370
[offset 90]

0x68 (104)

1 to 4

6

4

4006

uint
RWES

[`Rt;L]
[ rt.L]

Analog Input (1 to 4)

RTD Leads

Set to match the num-

ber of leads on the RTD

wired to this input.

[```2]

2 (1)

[```3]

3 (2)

2

372
[offset 90]

0x68 (104)

1 to 4

7

- - - -

4007

uint
RWES

[Unit]
[Unit]

Analog Input (1 to 4)

Units

Set the type of units the

sensor will measure.

[`A;tP]

Absolute Temperature

(1540)

[``rh]

Relative Humidity

(1538)

[`Pro]

Process (75)

[PWr]

Power (73)

Process

442
[offset 90]

0x68 (104)

1 to 4

0x2A (42)

5

4042

uint
RWES

[`S;Lo]
[ S.Lo]

Analog Input (1 to 4)

Scale Low

Set the low scale for pro-

cess inputs. This value,

in millivolts, volts or mil-

liamps, will correspond

to the Range Low output

of this function block.

-100.0 to 1,000.0

0.0

388
[offset 90]

0x68 (104)

1 to 4

0xF (15)

6

4015

float
RWES

[`S;hi]
[ S.hi]

Analog Input (1 to 4)

Scale High

Set the high scale for

process inputs. This

value, in millivolts, volts

or milliamperes, will

correspond to the Range

High output of this func-

tion block.

-100.0 to 1,000.0

20.0

390
[offset 90]

0x68 (104)

1 to 4

0x10 (16)

7

4016

float
RWES

Note:

Some values will be rounded off to fit in the four-character display .

Full values can be read with other interfaces .

Note:

If there is only one instance of a menu, no submenus will appear .

** These parameters/prompts are available in these menus with firmware revisions 6 .0 and

above .

R: Read

W: Write

E:

EEPROM

S:

User Set