Logic menu – Watlow EZ-ZONE RMC User Manual
Page 100
Watlow EZ-ZONE
®
RMC Module
•
97
•
Chapter 4 Setup Page
RMC Module • Setup Page
Dis-
play
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[trgt]
[trgt]
Counter (1 to 4)
Target Value
Set the value that will
turn the output value on.
0 to 9,999
9,999
4186
[offset 40]
0x82 (130)
1 to 4
0xE (14)
216
30014
uint
RWES
[`lAt]
[ LAt]
Counter (1 to 4)
Latching
Output latched.
No (59)
Yes (106)
No
4192
[offset 40]
0x82 (130)
1 to 4
0x11 (17)
218
30017
uint
RWES
[`LgC]
[`Set]
Logic Menu
[``Fn]
[ Fn]
Logic (1 to 4)
Function
Set the operator that
will be used to compare
the sources.
[`oFF]
Off (62)
[`And]
And (1426)
[nAnd]
Nand (1427)
[``or]
Or (1442)
[`nor]
Nor (1443)
[```E]
Equal To (1437)
[``nE]
Not Equal To (1438)
[`LAt]
Latch (1444)
[rs;ff]
RS Flip-Flop (1693)
[``or]
Or (1442)
Off
3744
[offset 80]
0x7F (127)
1 to 4
0x21 (33)
235
27033
uint
RWES
Note:
Some values will be rounded off to fit in the four-character display .
Full values can be read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0 and
above .
R: Read
W: Write
E:
EEPROM
S:
User Set