Timer menu – Watlow EZ-ZONE RMC User Manual
Page 53
Watlow EZ-ZONE
®
RMC Module
•
50
•
Chapter 3 Operations Page
RMC Module • Operations Page
Display
Parameter Name
Description
Range
Default
Modbus
Relative
Address
CIP
Class
Instance
Attribute
hex (dec)
Profibus
Index
Parameter
ID
Data
Type
& Read/
Write
[``o;u]
[ o.v]
Compare (1 to 4)
Output Value
View the value of this
function's output.
[`off]
Off (62)
[``on]
On (63)
- - - -
4018
[offset 40]
0x80
(128)
1 to 4
0xA (10)
- - - -
28010
uint
R
No Dis-
play
Compare (1 to 4)
Error
Read reported cause for
compare error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
- - - -
4024
[offset 40]
0x80
(128)
1 to 4
0x0D (13)
- - - -
28013
uint
R
[tMr]
[oPEr]
Timer Menu
[`Su;A]
[ Su.A]
Timer (1 to 4)
Value Source A
View the value of
Source A.
[`off]
Off (62)
[``on]
On (63)
- - - -
4332
[offset 50]
0x83
(131)
1 to 4
7
- - - -
31007
uint
R
[`Su;b]
[ Su.b]
Timer (1 to 4)
Value Source B
View the value of
Source B.
[`off]
Off (62)
[``on]
On (63)
- - - -
4334
[offset 50]
0x83
(131)
1 to 4
8
- - - -
31008
uint
R
[``E;t]
[ E.t]
Timer (1 to 4)
Elapsed Time
View the value of this
function's elapsed time.
0 to 9,999.000 seconds
- - - -
4350
[offset 50]
0x83
(131)
1 to 4
0x10 (16)
- - - -
31016
float
R
[``o;u]
[ o.v]
Timer (1 to 4)
Output Value
View the value of this
function's output.
[`off]
Off (62)
[``on]
On (63)
- - - -
4338
[offset 50]
0x83
(131)
1 to 4
0xA (10)
- - - -
31010
uint
R
No Dis-
play
Timer (1 to 4)
Error
Read reported cause for
timer error
None (61)
Open (65)
Shorted (127)
Measurement Error (140)
Bad Cal Data (139)
Ambient Error (9)
RTD Error (141)
Fail (32)
Math Error (1423)
Not Sourced (246)
Stale (1617)
- - - -
4354
[offset 50]
0x83
(131)
1 to 4
0x12 (18)
- - - -
31018
uint
R
Note:
Some values will be rounded off to fit in the four-character display . Full values can be
read with other interfaces .
Note:
If there is only one instance of a menu, no submenus will appear .
** These parameters/prompts are available in these menus with firmware revisions 6 .0
and above .
R: Read
W: Write
E: EEPROM
S: User Set