PLCopenPlus Function Blocks for Motion Control 2013-04-13
331
and the data was found to be corrupted. The alarm history
has been lost. NOTE: this alarm also occurs if the
configured size of the alarm history has been changed.
app
440A
000C
The position and torque scales specified in the
configuration file have different signs. As a result, a
positive acceleration results in a negative torque, and
position limits are opposite in sign as the torque limits.
app
440A
000F
The axis was temporarily disconnected from the servo
network during reset. During this time, the feedback data
is not valid and the axis cannot be moved.
app
440A
0011
The network I/O was temporarily disconnected from the
servo network during reset. During this time, any network
I/O state change will be unobservable to the controller.
app
440A
0019
The system was rebooted by the user.
app
440A
001A
The system failed to shut down gracefully during a reboot,
although the reboot did occur. This does not necessarily
indicate that the software is damaged.
app
440B
0001
The controller is running out of memory. Memory should
be freed as soon as possible. Try closing connections to
the controller or stopping scripts.
app
440B
0003
The largest free memory block is approaching the critical
level. Memory should be freed as soon as possible. Try
closing connections to the controller or stopping scripts.
app
440C
0105
Reserved
app
440C
1032
The configuration file version is not compatible with the
fimware version. Please use the configuration tool to
update the configuration files to match the the firmware
version.
app
440C
1034
Some function blocks are not supported by the controller
firmware. If these function blocks are used in the PLC
application, then their ErrorID will always equal 60909. If
these function blocks are needed, then please upgrade the
controller's firmware.
app
4501
0000
A user script task posted a warning directly.