beautypg.com

Installation instructions and safety precautions, 1 abbreviations, 2 installation preparations – CommScope ATC300-2000 User Manual

Page 30

background image

Section 2

Installation Instructions and Safety Precautions

2.0 Section Overview

This section covers installation procedures for mounting and grounding the ATC300-1000/2000 con-
troller chassis, as well as safety precautions.

2.1 Abbreviations

AWG

American Wire Gauge

2.2 Installation Preparations

Warnings:

This equipment should only be installed by trained personnel.

Do not connect or disconnect cables during lightning activity.

Preparation:

Remove the ATC300-1000/2000 controller from the packaging container (also see ESD precau-
tions in the introduction of this document).

Verify availability of power, either –48 V battery or +24 V power supply.

Tools and Parts:

14–AWG multi-strand copper wire for power connection, using color coding as specified at the
installation site.

10–AWG multi-strand copper wire, using appropriate color coding as specified at the installation
site.

Ring-torque terminal for a 1/4” stud.

Crimping tool for ring-torque terminal.

Four mounting screws to mount the controller chassis onto the rack.

6” adjustable wrench.

1/8” flat-blade screwdriver.

• Wire

stripper.