Drive plc developer studio – Lenze DDS v2.3 User Manual
Page 212

Drive PLC Developer Studio
Resources
8-22
l
DDS EN 2.3
Tip!
Note that data inconsistencies may occur if analog input 1 is used several times within the cyclical
task.
•
As the process image is updated every 3 ms within the 40 ms of cyclical task processing,
there may be different input values for analog input 1.
Event-controlled task (EVENT)
•
If system organization units are used in one event-controlled task only, their process image
will be generated in the event-controlled task.
•
If the same system organization units (that are not also used in a time-controlled task) are
used in two event-controlled tasks, their process image will be generated in the cyclical task.
Tip!
For further information about tasks, refer chapter 8.8, “ Task configuration” .
Interrupt-controlled task
•
If system organization units are used in one event-controlled task only, their process image
will be generated in the event-controlled task.
•
If the same system organization units (that are not also used in a time-controlled task) are
used in an event-controlled and an interrupt-controlled task, their process image will be
created in the cyclical task.