Control connection details
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
44
24V
24V supply
24VDC ±25%
20mA
Connection of the supply voltage
for the module and the reference
potential of the analog signals
112 AGND/0V
Reference potential
for analogue signals
111 10V REF
+10V
Reference voltage
+10V, 5mA
Connection of reference voltage
from frequency inverter
114
AIN1
Analog input 1
U= -
10 … +10V, R
i
=2MΩ
Resolution 10Bit
Signal IN
Signal OUT
Terminal
Value Terminal
Value
114
-10V
117
+10V
114
+10V
117
0V
116
-10V
118
+10V
116
+10V
118
0V
The conversion of the analog
signals is inverted.
Assignment of the functions of the
analog input signals is made via
parameter P400[...] of the
frequency inverter.
116
AIN2
Analog input 2
117
AOUT1
Analog output 1
Resolution: 10Bit
Precision: 0.25V
Load capacity with signal:
0…10V: ≤ 10mA
118
AOUT2
Analog output 2
Potential isolation
C1
DIN1
Digital input 1
Relay input:
Low: 0-5V (2.8kOhm)
High: 18-30V (1.6kOhm)
Reaction time max. 7ms
Assignment of the functions of the
analog output signals is made via
parameter P434[...] of the
frequency inverter.
C2
DIN2
Digital input 2
40 GND /0V
Reference potential
for digital signals
R14
R1 NO
Relay 1.1
Normally closed
contact
Relay input:
Low: 0-5V (2.8kOhm)
High: 18-30V (1.6kOhm)
Reaction time max. 7ms
Mechanical
lifetime:
1x10
8
(1 billion) OPS
(Operations)
Electrical:
3x10
5
(3 million) OPS
(Operations)
Relay (changeover) with function:
Closer:
R11 / R14
Opener:
R11 / R12
R12
R1 NC
Relay 1.2
Normally opened
contact
R11
Relay 1.3
Common contact
R24
R2 NO
Relay 2.1
Normally closed
contact
Relay (changeover) with function:
Closer:
R21 / R24
Opener:
R21 / R22
R22
R2 NC
Relay 2.2
Normally opened
contact
R21
Relay 2.3
Common contact