6 assignment of functions, 7 broadcast operation – NORD Drivesystems BU0200 User Manual

Page 88

background image

3 Options

BU 0200 GB-4411

Subject to technical alterations

87

3.4.3.6

Assignment of functions

The assignment of functions for the digital and analog inputs and outputs is made in the following
parameters of the frequency inverter.

Parameter

Function designation

P400

Setpoint input function

P401

External analog input mode

P402

External analog input matching 0%

P403

External analog input matching 100%

P417

Offset analog output

P418

Function analog output

P419

Standardisation, analog output

P480

Function of BUS IO In bits

P481

Function of BUS IO Out bits

P482

Standardisation of BUS IO Out bits

P483

Hysteresis of BUS IO Out bits

The parameters of the IO module are used exclusively for information and testing purposes. Exception:

(P161) (→ Matching of the filter settings for the IO signals),

(P162) (→ Toggling between normal and broadcast operation) and

(P163) (→ Inversion of the analog output signal)

3.4.3.7

Broadcast operation

In "broadcast mode" (parameter (P162)) it is possible to make up to two I/O - modules available in parallel
for a maximum of four frequency inverters. The prerequisite for this is that the FIs are on a common system
bus and no frequency inverter address has been assigned more than once (see Section 5.2.2.2).

Therefore the frequency inverters jointly access the I/Os and evaluate the input signals according to their
own FI parameterisation. Output signals from the frequency inverters which are sent to the common I/O
module are linked by a logical "OR" within the module. I.e. a digital output (SK TU4-IOE-

…) is set as soon

as one of the four frequency inverters addresses it. In addition, the highest analog value is provided via the
analog output of the I/O extension.