NORD Drivesystems BU0200 User Manual
Page 224
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
223
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P541
Set relays
(Set digital output)
S
000 ... 1FF
(hex)
{ 000 }
This function provides the opportunity to control the relay and the digital outputs independently
of the frequency inverter status. To do this, the relevant output must be set to the function
"External control".
This function can either be used manually or in combination with a bus control.
Bit 0 = Digital output 1
Bit 1 = Bus/AS-i Out Bit 0
Bit 2 = Bus/AS-i Out Bit 1
Bit 3 = Bus/AS-i Out Bit 2
Bit 4 = Bus/AS-i Out Bit 3
Bit 5 = Bus/An/Dig Out Bit 4,
“Bus/Analog /Digital Out Bit 4”
Bit 6 = Bus/An/Dig Out Bit 5,
"Bus/Analog /Digital Out Bit 5"
Bit 7 = Bus dig out 7, "Bus digital output 7"
Bit 8 = Bus dig out 8, "Bus digital output 8"
Bit 9 = PZD - Bit 10
Bit 10 = PZD - Bit 13
Bit 11 = Digital output 2
Bit 8
Bits 7 -4
Bits 3 -0
Min. value
0
0
0000
0
0000
0
Binary
hex
Max. value
1
1
1111
F
1111
F
Binary
hex
Changes which are made to the settings are not saved in the EEPROM. After "Power ON" of
the frequency inverter, the parameter is therefore in the default setting.
Setting
of the value via …
BUS:
The corresponding hex value is written into the parameter, thereby
setting the relay or digital outputs.
SimpleBox:
The hexadecimal code is entered directly if the SimpleBox is used.
ParameterBox:
Each individual output can be separately called up in plain text and
activated.
P542
[-01]
[-02]
Set analog out
(Set analog output)
S
0.0 ... 10.0 V
{ all 0.0 }
[-01] =
First IOE, AOUT of the first I/O extension (SK xU4-IOE)
[-02] =
Second IOE, AOUT of the second I/O extension (SK xU4-IOE)
... only with
SK CU4-IOE or
SK TU4-IOE
The analog output of the FI can be set with this function, independently of the actual operating
state. To do this, the relevant analog output must be set to the function "External control"
(P418 = 7).
This function can either be used manually or in combination with a bus control. The value set
here will, once confirmed, be produced at the analog output.
Changes which are made to the settings are not saved in the EEPROM. After "Power ON" of
the frequency inverter, the parameter is therefore in the default setting.