6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
191
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter set
P326
Ratio encoder
(Encoder transformation ratio)
S
0.01 ... 100.00
{ 1.00 }
If the incremental encoder is not mounted directly onto the motor shaft, then the respectively
correct transformation ratio of motor speed to encoder speed must be set.
speed
Encoder
speed
Motor
P326
Only when P325 = 1, 2, 3 or 4, therefore not in Servo mode (motor speed control)
P327
Speed slip error
(Speed slip error, speed control)
S
P
0 ... 3000 rpm
{ 0 }
The limit value for a permitted maximum slip error can be set. If this value is reached, the FI
switches off and indicates error E013.1.
0 = OFF
Only when P325 = 0, therefore in Servo mode (motor speed control)
P328
Speed slip delay
(Speed slip error delay)
S
P
0.0 ... 10.0 s
{ 0.0 }
In case the permissible slip error defined in (P327) is exceeded, the display of the error
message E013.1 is suppressed within the limits which can be set here.
0 = OFF