beautypg.com

1 details of the control connections – NORD Drivesystems BU0200 User Manual

Page 108

background image

3 Options

BU 0200 GB-4411

Subject to technical alterations

107

3.5.4.1

Details of the control connections

Terminal/

Name

Function

Data

Description / wiring suggestion

Parameter

1

+10V

2

10V reference
voltage

10V ± 0.1V

Max.
load 20mA

Potentiometer supply voltage

-

3

AIN1+

Analog input 1

positive

Version as differential
input

Resolution 12Bit

Accuracy: 0.1V

Functions:

0V

… 10V / -10V … +10V /

0mA

… 20mA / 4mA … 20mA

(selection via DIP switch)

P400
P176

5

AIN1-

Analog input 1

negative

4

AIN2+

Analog input 2

positive

Version as differential
input

Resolution: 12Bit
Accuracy: 0,1V

P400
P176

6

AIN2-

Analog input 2

negative

7

0V-A

8

Analog Ground

Reference potential for analog
signals

-

9

AOUT

Analog Out

Resolution: 10Bit
Accuracy 0.25V

Load capacity with signal:
0…10V: ≤ 10mA
0…20mA : ≤ 20mA*
* (with 5V)

Functions:

0V

… 10V / -10V … +10V /

0mA

… 20mA / 4mA … 20mA

(selection via DIP switch)

P418
P176

10

PE

PE

-

Potential separation

11

24V

12

13

external 24V supply

(module, system bus level)

24VDC ±20%

≈ 1100mA
protected against reverse
polarity


Max. permissible current
load: 3A

Connection for module supply
voltage and 24V source for the
digital inputs (DIN1 to DIN4)

-

15

0V

17

18

GND
Reference potential
for digital signals

-

14

Sys+

System bus
data cable +

System bus
interface

-

16

Sys-

System bus
data cable -

-

19

DIN1

Digital input 1

(I/O IO extension DIN1)

Low 0V ... 5V
High 15V ... 30V

R

i

= 8.1k

Input capacitance 10nF

Scan rate 1ms,
Reaction time 1ms

The functions must be assigned in
parameter P480. The settings for
the first IOE are made in the arrays
[-05 / -07] and for the second IOE
in the arrays [-01, -03].
Inputs compliant with
EN 61131-2,

Type 1

P480
P174

20

DIN3

Digital input 3

(I/O IO extension DIN3)

P480
P174