NORD Drivesystems BU0200 User Manual
Page 200
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
199
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P412
Nom.
val.
process ctrl.
(Nominal value process controller)
S
P
-10.0 ... 10.0 V
{ 5.0 }
Fixed specification of a setpoint for the process controller that will only occasionally be altered.
Only with P400 = 6 or 7 (PID process controller). Further technical details can be found in
Section 9.2.
P413
PI control P comp.
(P-component of PI controller)
S
P
0.0 ... 400.0 %
{ 10.0 }
This parameter is only effective when the function PI controller actual frequency is selected.
The P-component of the PI controller determines the frequency jump if there is a control
deviation based on the control difference.
For example: At a setting of P413 = 10% and a control difference of 50%, 5% is added to the
actual setpoint.
P414
PI control I comp.
(I-component of PI controller)
S
P
0.0 ... 3000.0 %/s
{ 10.0 }
This parameter is only effective when the function PI controller actual frequency is selected.
In case of a control deviation, the I-component of the PI controller determines the frequency
change, dependent on time.
Note:
In contrast to other NORD series, parameter P414 is smaller by a factor of 100
(Reason: better setting ability with small I-components).
P415
Process control control limit
(Process controller control limit)
S
P
0 ... 400.0 %
{ 10.0 }
This parameter is only effective when the function PI process controller is selected. This
determines the control limit (%) after the PI controller.
For further details, see Section 9.2.
P416
Ramptime PI setpoint
(Ramp time PI setpoint value)
S
P
0.00 ... 99.99 s
{ 2.00 }
This parameter is only effective when the function PI process controller is selected.
Ramp for PI setpoint
P417
[-01]
[-02]
Offset analog output
(Offset analog output)
S
P
-10.0 ... 10.0 V
{ all 0.0 }
[-01] =
First IOE, AOUT of the first I/O extension (SK xU4-IOE)
[-02] =
Second IOE, AOUT of the second I/O extension (SK xU4-IOE)
... only with
SK CU4-IOE or
SK TU4-IOE
In the analog output function an offset can be entered to simplify the processing of the analog
signal in other equipment.
If the analog output has been programmed with a digital function, then the difference between
the switch-on point and the switch-off point can be set in this parameter (hysteresis).
P418
[-01]
[-02]
Function Analog out
(Analog output function)
S
P
0 ... 33
{ all 0 }
[-01] =
First IOE, AOUT of the first I/O extension (SK xU4-IOE)
[-02] =
Second IOE, AOUT of the second I/O extension (SK xU4-IOE)