NORD Drivesystems BU0200 User Manual
Page 234
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
233
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P727
Mechanical power
(Mechanical power)
-99.99 ... 99.99 kW
Displays the actual calculated effective power of the motor. Basis for calculation is the motor
data P201...P209 ... .
P728
Input voltage
(Mains voltage)
0 ... 1000 V
Displays the actual mains voltage at the FI input.
P729
Torque
(Torque)
-400 ... 400 %
Displays the actual calculated torque. Basis for calculation is the motor data P201...P209 ... .
P730
Field
(Field)
0 ... 250 %
Displays the actual field in the motor as calculated by the inverter. Basis for calculation is the
motor data P201...P209 ... .
P731
Parameter set
(Actual parameter set)
0 ... 3
Shows the actual operating parameter set.
0 = Parameter set 1
1 = Parameter set 2
2 = Parameter set 3
3 = Parameter set 4
P732
Phase U current
(U phase current)
S
0.0 ... 999.9 A
Displays the actual U phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P733
Phase V current
(V phase current)
S
0.0 ... 999.9 A
Displays the actual V phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P734
Phase W current
(W phase current)
S
0.0 ... 999.9 A
Displays the actual W phase current.
NOTE:
This value can deviate from the value in P719, due to the measurement procedure
used, even with symmetrical output currents.
P735
Speed encoder
(Encoder speed)
S
-9999 ... 9999 rpm
Displays the actual rotation speed supplied by the incremental encoder. For this, P301 must be
correctly set.
P736
D.c. link voltage
(DC link voltage)
0 ... 1000 V DC
Displays the actual link voltage.