8 information (frequency inverter) – NORD Drivesystems BU0200 User Manual
Page 230
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
229
6.1.8
Information (Frequency inverter)
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P700
[-01]
...
[-03]
Present operating status
(Present operating status)
0.0 ... 21.4
Display of current messages for the actual operating status of the frequency inverter such as
errors, wanings or the cause of a switch-on block. For details of messages see Section 7
[-01] = Current fault, shows the currently active (unacknowledged) error (Section 7.2.1)
[-02] = Actual warning, shows any current warning message (Section 7.3)
[-03] = Reason FI blocked, shows the reason for a currently active switch-on block
(Section 7.4)
Note
SimpleBox:Only warning messages and errors can be displayed with the Simplebox. Display of
the messages is encoded. For the description of the codes (warning/error numbers), please
refer to the tables in Sections 7.2.1 and 7.3.
ParameterBox: the ParameterBox displays the messages in plain text. The reason for any
switch-on block can also be displayed.
Bus: The display of error messages at bus level is in decimal integer format. If the value is
divided by 10, the display corresponds to the description in Section 7.2.
Example: Display: 20 → Error number: 2.0
P701
[-01]
...
[-05]
Last fault
(Last fault 1 ... 5)
0.0 ... 21.4
This parameter stores the last 5 faults. (Details Section 7)
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P702
[-01]
...
[-05]
Freq. last error
(Last frequency fault 1 ... 5)
S
-400.0 ... 400.0 Hz
This parameter stores the output frequency that was being delivered at the time the fault
occurred. The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P703
[-01]
...
[-05]
Current. last error
(Last current fault 1 … 5)
S
0.0 ... 999.9 A
This parameter stores the output current that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.
P704
[-01]
...
[-05]
Volt. last error
(Last voltage fault 1 ... 5)
S
0 ... 600 V AC
This parameter stores the output voltage that was being delivered at the time the fault occurred.
The values of the last 5 errors are stored.
With the SimpleBox, the corresponding memory location 1...5- (Array parameter) must be
selected and confirmed using the OK key to read the stored error code.