NORD Drivesystems BU0200 User Manual
Page 102
3 Options
BU 0200 GB-4411
Subject to technical alterations
101
Details of the control connections
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
43
VO/24V
24V supply
24VDC ±10%
max. 420mA (total)
integrated
short-circuit monitoring,
limited overtemperature
and overload monitoring
Supply voltage (output) to supply
an SK 2x5E or other module with
24V.
-
40
GND/0V
Reference potential
-
43
VO/24V
24V supply
-
40
GND/0V
Reference potential
-
43
VO/24V
24V supply
-
40
GND/0V
Reference potential
-
11
10V REF
+10V
reference voltage
10V ± 0.2V
Max.
load 5mA
Only in combination with
SK TU4-24V-
…
For connection of potentiometer
5 -
10kΩ.
A 500Ω burden resistor for the
evaluation of 0/4 - 20mA signals is
contained in the enclosed bag.
-
14
AIN1+
Analog input
positive
0 … 10V,
Resolution: 8Bit
Accuracy: 0.2V
-
12 AGND/0V
Analog Ground
Reference potential for
analog signals
-
B1
DOUT BUS
(FOUT)
Frequency output
SPS compatible in
compliance with
EN61131-2
Low: 0V, High: 24V
Pulse frequency: ~ 1 -
32kHz
Pulses for evaluation via the digital
input function P420 [02]/[03] =
26/27 and the analog meaning in
P400 [-06]/[-07].
With the use of an SK TU4-24V-... this
outputs the setpoint value of the analog
input.
With the use of an SK TU4-POT-... this
outputs the setpoint value of the
integrated potentiometer.
P420
P400
B2
ON-L
Digital output, enable
left
Only in combination with
SK TU4-POT-
…
Control via "Left" key
P420
B3
ON-R
Digital output, enable
right
Only in combination with
SK TU4-POT-
…
Control via "Right" key
P420
40
GND/0V
Reference potential
-
Potential separation
PE
PE, Earth
Does not need to be connected.
Is already connected to the module
housing.
-
Mains connection, 100 - 240V or
380 - 500V, depending on the
module
-
L1
Mains connection
1.Phase
-
-
L2/N
Mains connection
2. Phase
-