Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P543
[-01]
...
[-03]
Bus actual value
1… 3
(Actual bus value 1)
S
P
0 ... 24
{ [-01] = 1 }
{ [-02] = 4 }
{ [-03] = 9 }
In this parameter the returned value on bus actuation can be selected.
NOTE:
For further details, please refer to the relevant bus manual or the description for
(P418). (Values from 0% … 100% correspond to 0000
hex
… 4000
hex
)
For standardisation of the actual values: See also (Section 9.10).
[-01] = Actual bus value 1
[-02] = Actual bus value 2 (only for PPO type 2 or 4)
[-03] = Actual bus value 3 (only for PPO type 2 or 4)
(Definition of frequencies, see Section. 9.11)
Possible setting values:
0 = Off
1 = Actual frequency
(x=4000
hex
*f[Hz]/(P105))
2 = Actual speed
(x=4000
hex
*n(rpm]/(P202))
3 = Current
(x=4000
hex
*I[A]/(P203))
4 = Torque current (100% = P112)
(x=4000
hex
*Iq[A]/(P112)*100/
√((P203)²+(P209)²)
5 = Digital IO status
9
6 = ... 7 reserved
8 = Setpoint frequency
(x=4000
hex
*fs[Hz]/(P105))
9 = Error code
10 = ... 11 reserved
12 = Bus IO Out Bits 0..-7
13 = ... 16 reserved
17 = Value analog input 1,
SK2x0E: Analog input 1 (P400[-01]),
SK2x5E: AIN1 of the first I/O extension
SK xU4-IOE (P400 [-03]))
18 = Value analog input 2,
SK2x0E: Analog input 2 (P400[-02]),
SK2x5E: AIN2 of the first I/O extension
SK xU4-IOE (P400 [-04]))
19 = Freq
master value (P503)
"Setpoint frequency master value"
(x=4000
hex
*fs[Hz]/(P105))
20 = Set freq after ramp ,
"Setpoint frequency from ramp master
value"
(x=4000
hex
*fsnr[Hz]/(P105))
21 = Act. freq. wo. slip,
"Actual frequency without slip master
value"
(x=4000
hex
*f-f2[Hz]/(P105))
22 = Speed encoder
"Speed from encoder"
(x=4000
hex
*n[rpm]/(P201)*(60/p))
p=number of pole pairs
23 = Actual with slip
(SW V1.3 and above)
"Actual frequency with slip"
(x=4000
hex
*f[Hz]/(P105))
24 = Master actual
(SW V1.3 and above)
"Actual frequency master value with slip"
(From SW V1.3)
(x=4000
hex
*f[Hz]/(P105))
9
The assignment of the dig. inputs for P543 = 5
Bit 0 = DigIn 1
(FI)
Bit 1 = DigIn 2
(FI)
Bit 2 = DigIn 3
(FI)
Bit 3 = DigIn 4
(FI)
Bit 4 = PTC input
(FI)
Bit 5 = DigIn 5
(DI1, 1.
SK…IOE)
Bit 6 = DigIn 6
(DI2, 1. SK…IOE)
Bit 7 = DigIn 7
(DI3, 1. SK…IOE)
Bit 8 = DigIn 8
(DI4, 1.
SK…IOE)
Bit 9 = reserved
Bit 10 = reserved
Bit 11 = reserved
Bit 12 = DigOut 1
(FI)
Bit 13 = mech. brake
(FI)
Bit 14 = DigOut 2
(DO1, 1.
SK…IOE)
Bit 15 = DigOut 3
(DO2, 1. SK…IOE)