1 simplebox, sk csx-3h – NORD Drivesystems BU0200 User Manual
Page 133
SK 200E Manual for frequency inverters
132
Subject to technical alterations
BU 0200 GB-4411
4.2.1
SimpleBox, SK CSX-3H
This option is used as a simple parameterisation, display and control tool for the SK 2xxE frequency
inverter.
Features
4-digit, 7-segment LED display
Complete parameterisation of the frequency inverter.
Direct control of a frequency inverter
Displays
the
active
parameter
set
during
parameterisation and operation and the operating
value set in P001.
After the SimpleBox has been connected and the mains switched on, horizontal lines appear in the 4-digit
7-segment display. This display signals the operational readiness of the frequency inverter.
If a creep frequency value is pre-set in parameter P113, or a minimum frequency or setpoint value is pre-set
in P104, the display flashes with this initial value.
If the frequency inverter is enabled, the display changes automatically to the operating value selected in
parameter >Selection Display value< P001 (factory setting = current frequency).
The actual parameter set in use is shown by the 2 LEDs next to the display on the left in binary code.
NOTE
The digital frequency setpoint is factory set to 0Hz. To check whether the motor is working, a
frequency setpoint must be entered with the
/
key or a jog frequency via the
respective parameter >Jog frequency< (P113).
Settings should only be made by qualified personnel, in strict compliance with the warning
and safety information.
ATTENTION:The motor may start immediately after pressing the START key
!
NOTE
The SimpleBox cannot be used to control or parameterise the optional modules (e.g.:
SK xU4-
…)