Parameter list - inverter information (selection)
Parameter
Description
Settings / functions (selection)
P700
Actual operating
status
Display of current messages for the actual operating
status of the frequency inverter such as errors,
warnings or the cause of a switch-on block.
Selection:
Actual error (P700, [-01]
Actual warning (P700, [-02]
Reason for switch-on block (P700, [-03])
Error group:
1 / 2 = Overtemperature of inverter /
motor
3 / 4 = Overcurrent error
5 = Overvoltage error
16 = Motor phase monitoring
19…= Parameter identification error
P701
Last error
Displays the last 5 frequency inverter errors.
Selection:
Last error (P701, [ -01])
Second to last error (P701, [-02])
See P700
P707
Software version
Displays the firmware version / Inverter revision
Selection:
Software version (P707, [-01])
Revision (P707, [-02])
P708
Digital
input
status
Shows the switching status of the digital inputs.
Bit 0 = DIN 1
Bit 1 = DIN 2
…
P709
Analog
input
voltage
Displays the measured analog input value.
Selection input:
Poti P1 (P400, [-01]) - SK 2x5E
Poti P2 (P400, [-02]) - SK 2x5E
AIN1 (P400, [-01]) - SK 2x0E
AIN2 (P400, [-02]) - SK 2x0E
DIN 2 (P400, [-06])
DIN 3 (P400, [-07])
P719
Actual current
Displays the actual output current.
P740
Process
data
Bus In
Displays the actual control word and the setpoints.
[-01] = STW (Source P509)
[-
02…-04] SW 1…3 (Source P510[-01]
[-
11…-13] SW 1…3 (Source P510[-02]
P749
DIP switch status
Displays the actual DIP switch setting (S1).
Bit 0 = DIP switch 1
Bit 1 = DIP switch 2
…