NORD Drivesystems BU0200 User Manual
Page 125
SK 200E Manual for frequency inverters
124
Subject to technical alterations
BU 0200 GB-4411
Control connection details
Terminal/
Name
Function
Data
Description / wiring suggestion
Parameter
1
24V
2
9
10
24V supply
(Module and system bus
level)
24VDC ±20%
≈ 100 mA
reverse polarity protected
Max. permissible current
load: 500mA
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN8)
via DC/DC converter to
Terminal 11.
-
3
DIN5
Digital input 5
(I/O EtherCAT DIN5)
Low 0V ... 5V
High 15V ... 30V
R
i
= 10k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per
EN 61131-2 Type 1
Each digital input has a reaction
time of 1ms.
P174
4
DIN7
Digital input 7
(I/O EtherCAT DIN7)
P174
5
DIN6
Digital input 6
(I/O EtherCAT DIN6)
P174
6
DIN8
Digital input 8
(I/O EtherCAT DIN8)
P174
7
0V
8
GND
Reference potential
for digital signals
As for terminal 15
GND for system bus and digital
inputs (DIN1 to DIN8)
via connection ofDC/DC converter
to Terminal 15
-
11 24V
12
13
24V supply
(Module and system bus
level)
As for terminal 1
Max. permissible current
load: 3A
Connection of supply voltage for
module and 24V source for supply
of the digital inputs (DIN1 to DIN8)
-
15
0V
17
18
GND
Reference potential
for digital signals
-
14
Sys+
System bus
data cable +
System bus
interface
-
16
Sys-
System bus
data cable -
-
19
DIN1
Digital input 1
(I/O EtherCAT DIN1)
Low 0V ... 5V
High 15V ... 30V
R
i
= 8.1k
Input capacitance 10nF
Scan rate 1 ms
Inputs as per
EN 61131-2
Type 1
Each digital input has a reaction
time of 1ms.
P174
20
DIN3
Digital input 3
(I/O EtherCAT DIN3)
P174