NORD Drivesystems BU0200 User Manual
Page 153
SK 200E Manual for frequency inverters
152
Subject to technical alterations
BU 0200 GB-4411
Details of DIP switch S1: 5/4 and 3
Applies to devices SK 20xE, SK 21xE (without on board AS interface)
DIP
Functions as per the list of digital functions (P420)
Functions as per the list of
analog functions (P400)
5
4
3
Dig 1
Dig 2
Dig 3
Dig 4**
Poti 1***
Poti 2***
off
off
off
(P420 [01])*
{01}
"Enable R"
(P420 [02])*
{02}
"Enable L"
(P420 [03])*
{04}
“Fixed freq. 1"
=5Hz (P465[01])
(P420 [05])*
{04}
“Fixed freq. 2"
=10Hz (P465[02])
(P400 [01])*
{01}
" F setpoint"
(P400 [02])*
{15}
"Ramp"
off
on
off
{01}
"Enable R"
{02}
"Enable L"
{26}
"F setpoint"
{12}
"Quit"
{05}
"F max"
{04}
"F min"
on
off
off
{45}
"3-on"
{49}
"3-off"
{47}
"Freq. +"
{48}
"Freq. -"
{05}
"F max"
{15}
"Ramp"
on
on
off
{50}
„F Arr Bit0
=5Hz (P465[01])
{51}
„F Arr Bit1“
=10Hz (P465[02])
{52}
„F Arr Bit2“
=20Hz (P465[03])
{53}
„F Arr Bit3“
=35Hz (P465[04])
{05}
"F max"
{15}
"Ramp"
off
off
on
The functions of the digital inputs are inactive (control via system bus), however, the
settings made in parameters (P420 [01 … 04]) result in the activation of the
correspondingly parameterised input, for the functions designated with ..² in the function
list (e.g.: {11}²= "Quick stop).
(P400 [01])
{
01} " F setpoint"
(P400 [02])
{15}
"Ramp"
(P420 [01])
no function
(P420 [02])
no function
(P420 [03])
{04} Fixed freq. 1"
=5Hz (P465[01])
(P420 [04])
{05} Fixed freq. 2"
=10Hz (P465[02])
off
on
on
{14}
"Remote
control"
"Encoder track
A"
"Encoder track
B"
{01}
"Enable R"
{01}
"F
setpoint"
{05}
"F max"
on
off
on
{14}
"Remote
control"
{01}
"Enable R"
{10}
"Block"
{66}
"Release
brake"
{01}
"F
setpoint"
{05}
"F max"
on
on
on
{14}
"Remote
control"
{51}
„F Arr Bit1“
=10Hz (P465[02])
{52}
„F Arr Bit2“
=20Hz (P465[03])
{53}
„F Arr Bit3“
=35Hz (P465[04])
{05}
"F max"
{15}
"Ramp"
Explanation: (values underlined in brackets) = (relevant parameter / source of function), e.g.: Parameter (P420[01])
{curly brackets}
= {Function} e.g.: {01} "Enable Right"
(See also Section 6
: → Table behind parameter (P420), (P400) or (P434))
* Default setting
** only if available (Devices without function "Safe Stop")
*** only with SK 2x5E models, SK 2x0E models have no potentiometers P1 and P2
Applies to devices SK 22xE, SK 23xE (with on board AS interface)
DIP
Functions as per the list of digital functions (P420)
Functions as per the list of digital outputs (P434)
5
4
3
ASi
In1
ASi
In2
ASi
In3
ASi
In4
ASi
Out1
ASi
Out2
ASi
Out3
ASi
Out4
off off off
(P480 [01])*
{01}
"Enable
R"
(P480 [02])*
{02}
"Enable
L"
(P480 [03])
{04}
Fixed
freq. 1"
=5Hz (P465[01])
(P480 [04])*
{12}
"Quit"
(P481 [01])*
{07}
"Error"
(P481 [02])*
{18}
"Standby"
"DigIn1"
"DigIn2"
off on off
{04}
"Fixed
freq. 1"
=5Hz (P465[01])
{05}
"Fixed
freq. 2"
=10Hz (P465[02])
{06}
"Fixed
freq. 3"
=20Hz (P465[03])
{07}
"Fixed
freq. 4"
=35Hz (P465[04])
{07}
"Error"
{18}
"Standby"
"DigIn1"
"DigIn2"
on off off
{01}
"Enable R"
{02}
"Enable L"
{47}
"Freq. +"
{48}
"Freq. -"
{07}
"Error"
{18}
"Standby"
"DigIn1"
"DigIn2"
on on off
{51}
"F Arr B1"
=10Hz (P465[02])
{52}
"F Arr B2"
=20Hz (P465[03])
{53}
"F Arr B3"
=35Hz (P465[04])
{14}
"Remote
control"
{07}
"Error"
{18}
"Standby"
"DigIn1"
"DigIn2"
off off on
The functions of the digital inputs are inactive (control via system bus),
however, the settings made in parameters (P480 [01 … 04]) result in the
activation of the correspondingly parameterised bits, for the functions
designated with ..² in the function list (e.g.: {11}²= "Quick stop).
(P481 [01])
{07}
"Error"
(P481 [02])
{18}
"Standby"
"DigIn1"
"DigIn2"
(P480 [01])no
function
(P480 [02])
no function
(P480 [03])
{04}
Fixed
freq. 1"
=5Hz (P465[01])
(P480 [04])
{12}
"Quit"
off on on
{14}
"Remote
control"
{04}
"Fixed
freq. 1"
=5Hz (P465[01])
{05}
"Fixed
freq. 2"
=10Hz (P465[02])
{06}
"Fixed
freq. 3"
=20Hz (P465[03])
{07}
"Error"
{18}
"Standby"
"DigIn1"
"DigIn2"
on off on
{14}
"Remote
control"
{01}
"Enable R"
{47}
"Freq. +"
{48}
"Freq. -"
{07}
"Error"
{18}
"Standby"
"DigIn1"
"DigIn2"
on on on
{14}
"Remote
control"
{50}
"F Arr B0"
=5Hz (P465[01])
{51}
"F Arr B1"
=10Hz (P465[02])
{52}
"F Arr B2"
=20Hz (P465[03])
{07}
"Error"
{18}
"Standby"
"DigIn1"
"DigIn2"
Explanation: See table above
Note:
The functions of potentiometers P1 and P2 correspond to those of devices without an AS interface (see table above).
With DIP switches 5 and 4 in the OFF position (default setting), the digital inputs are also active. The functions then correspond to those of devices
without an AS interface (table above). In all other DIP switch combinations the functions of the digital inputs are deactivated.
ASi OUT1 and ASi OUT2 loop the signal level (High / Low) of digital inputs 1 and 2.