8 Technical data
8.1 General data for frequency inverter series SK 2xxE
Function
Specification
Output frequency
0.0 … 400.0Hz
Pulse frequency
3.0 … 16.0kHz, standard setting = 6kHz
Power reduction > 8kHz for 115/230V device, >6kHz for 400V device.
Typical overload capacity
150% for 60s, 200% for 3.5s
Protective measures against
Overtemperature of the frequency inverter,
overvoltage and undervoltage
Short-circuit, earthing fault,
overload, idling
Regulation and control
Sensorless current vector control (ISD), linear V/f characteristic curve,
automatic flux adaptation (energy-saving function)
Motor temperature monitoring
I
2
t motor, PTC / Bimetal switch
Digital input
3 or 4x, Low 0-5V, High 14-30V, R
i
= 9.5k
, C
i
= 10nF, cycle time = 4ms
Electrical isolation
Control terminals
Control outputs
Digital output:
Brake rectifier:
18-30V DC (according to VI 24V), max. 200mA, max. 100k
load
max. 0.5A choke current, voltage according to mains
Interfaces
Standard: RS 485 (USS)
RS 232 (Single Slave)
System bus
Option: Profibus, CANopen,
DeviceNet, AS-Interface,
EtherCAT, PROFINET
Efficiency of frequency inverter
approx. 95% according to size
Storage and transport temperature
-
25°C … +60 / 70°C
Operating / ambient temperature
-
25°C … +50°C, according to operating mode (Details: Section 8.3)
ATEX: -
20…+40°C (Details: Section 2.10)
Long-term storage
See Section 9.12.1
Protection class
IP55, optionally IP66 (S 4 only IP55 without or with IP66 special measures
according to Section 1.7)
Max. Installation altitude above sea
level
Up to 1000m:
No power reduction
1000...4000m:
1%/ 100m power reduction (up to 2000m overvoltage cat. 3)
2000...4000m:
Only overvoltage category 2 is complied with, external
overvoltage protection at the mains input is necessary
Ambient conditions
Transport (IEC 60721-3-2):
Vibration: 2M2
Operation (IEC 60721-3-3):
Vibration: 3M7;
Climate: 3K3 (IP55) / 3K4 (IP66)
Waiting period between
two power-up cycles
60 sec for all devices in normal operating cycle
Connection
terminals
Mains/motor/brake
resistance
4mm
2
flexible with wiring sleeves, 6mm
2
with rigid cable
Terminal screw
tightening
torque
1.2...1.5Nm
Control unit /System bus 2.5mm
2
, with wiring sleeves 1.5mm
2
RS485 / RS232
1x RJ12 (6-pin)
SK 2x0E:
24V - Output
(Terminal 43)
24V DC ±25%, max. 200mA
Digital outputs
24V DC ±25%, max. 20mA
SK 2x5E:
24V supply - input
(Terminal 44)
18…30V DC, at least 200...800mA according to load
Digital output
18…30V DC, according to supply voltage (Terminal 44) , max. 200mA