6 extra functions – NORD Drivesystems BU0200 User Manual
Page 212
6 Parameterisation
BU 0200 GB-4411
Subject to technical alterations
211
6.1.6
Extra functions
Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P501
Inverter name
(Inverter name)
A…Z
(char)
{ 0 }
Free input of a designation (name) for the device (max. 20 characters). With the the frequency
inverter can be uniquely identified for processing with NordCon software or within a network.
P502
[-01]
...
[-03]
Value Masterfunction
(Value master function)
S
P
0 ... 24
{ all 0 }
Selection of up to 3 master values of a Master for output to a bus system (see P503). The
assignment of these master values to the slave is carried out via (P546).
(for definition of frequencies see Section 9.11):
[-01] = Master value 1
[-02] = Master value 2
[-03] = Master value 3
Selection of possible setting values for master values:
0 = Off
1 = Actual frequency
2 = Actual speed
3 = Current
4 = Torque current
5 = Status Digital IO
6 = ... 7 reserved
8 = Setpoint frequency
9 = Error coder
10 = ... 11 reserved
12 = Bus IO Out Bits 0-7
13 = ... 16 reserved
17 = Value analog in 1, "Value of analog input 1"
SK2x0E: Analog input 1 (P400[-01]),
SK2x5E: AIN1 of the first I/O extension
SK xU4-IOE (P400 [-03]))
18 = Value analog in 2, "Value of analog input 2"
SK2x0E: Analog input 2 (P400[-02]),
SK2x5E: AIN2 of the first I/O extension
SK xU4-IOE (P400 [-04]))
19 = Freq.
master value, "Setpoint frequency
master value"
20 = Set freq after ramp master value,
"Setpoint frequency from ramp master value
21 = Act freq.wo.
slip master
"Actual frequency without slip master value"
22 = Speed encoder
23 = Actual with slip
(SW V1.3 and above)
"Actual frequency with slip"
24 = Master actual
(SW V1.3 and above)
"Actual frequency master value with slip"