6 Parameterisation

BU 0200 GB-4411

Subject to technical alterations

231

Parameter

Setting value / Description / Note

Device

Supervisor

Parameter
set

P709

[-01]

...

[-09]

Analog input voltage

(Voltage of analog inputs)

-100.0 ... 100.0 %

Displays the measured analog input value.

SK 2x0E*

SK2x5E**

[-01] = Analog input 1, function of analog

input 1 integrated into the FI

[-02] = Analog input 2, function of analog

input 2 integrated into the FI.

[-01] = Potentiometer 1, Internal potentiometer

P1 in the FI (Section 5.2.2), for setting
the maximum frequency, minimum
frequency and ramp time

[-02] = Potentiometer 2, as for potentiometer 1.

[-03] =

Ext. analog input 1, AIN 1 of the first I/O extension SK xU4-IOE

[-04] =

Ext. analog input 2, AIN 1 of the first I/O extension SK xU4-IOE

[-05] =

Setpoint module, in preparation

[-06] =

Analog function

2, analog function of the FI digital input 2

[-07] =

Analog function

3, analog function of the FI digital input 3

[-08] =

Ext. A.in 1 2nd IOE, "External analog input 1 2nd

IOE“,

AIN1 of the second I/O extension
(SK xU4-IOE) (= analog input 3).

[-09] =

Ext. A.in 2 2nd IOE, "External analog input 2 2nd IOE",

AIN2 of the second I/O extension
(SK xU4-IOE) (= analog input 4).

P710

[-01]

[-02]

Analog output volta.

(Analog output voltage)

0.0 ... 10.0 V

Displays the delivered value of analog output.

[-01] =

First IOE, AOUT of the first I/O extension (SK xU4-IOE)

[-02] =

Second IOE, AOUT of the second I/O extension (SK xU4-IOE)

P711

State of relays

(State of digital outputs)

00000 ... 11111

(bin)

or

00 ... FF

(hex)

Indicates the actual status of the digital outputs of the frequency inverter.

Bit 0 = Digital output 1
Bit 1 = mechanical brake
Bit 2 = Digital output 2
Bit 3 = reserved

Bit 4 = Digital output 1, IO extension 1
Bit 5 = Digital output 2, IO extension 1
Bit 6 = Digital output 1, IO extension 2
Bit 7 = Digital output 2, IO extension 2

Bits 7-4

Bits 3-0

Minimum value

0000

0

0000

0

Binary

hex

Maximum value

1111

F

1111

F

Binary

hex

SimpleBox: The binary bits are converted to a hexadecimal value and displayed.

ParameterBox: The bits are displayed with increasing values from right to left (binary).

P714

Operating time

(Operating time)

0.00 ... ___ h

This parameter shows the time for which the FI was connected to the mains and was ready for
operation.