NORD Drivesystems BU0200 User Manual
Page 280
8 Technical data
BU 0200 GB-4411
Subject to technical alterations
279
Size 2
Size 3
Device type:
SK 2xxE…
-301-340-A
-401-340-A
-551-340-A
-751-340-A
Nominal motor power
(4-pole standard motor)
400V
3.0 kW
4.0 kW
5.5 kW
7.5 kW
480V
4 hp
5 hp
7½ hp
10 hp
In
p
u
t
Mains voltage
3~ 400V
3 AC 380 ... 500V, -20% / +10%, 47 ... 63 Hz
Typical input current
at 400V
3~ rms
7.0 A
8.9 A
11.7 A
15.0 A
3~ FLA
6.3 A
8.0 A
10.3 A
13.1 A
Rec. mains fuse
1 AC
slow-acting [A]
16 A
16 A
20 A
25 A
Permissible
mains fuses (UL)
RK5 or faster
fuses,
min 230V/400V
10 A
30 A
30 A
30 A
Bussmann
FRS-R-10
FRS-R-30
FRS-R-30
FRS-R-30
Circuit breaker*
min. 230V/400V
10 A
25 A
25 A
25 A
O
u
tp
u
t
Output voltage
3~ 400V
3 AC 0 - Mains voltage
Nominal output
current at 400V
rms
7.5 A
9.5 A
12.5 A
16.0 A
Motor
Assembly**
7.5A
(45°C)
9.5A
(45°C)
12.5A
(45°C)
16.0A
(45°C)
Wall-mounted**
5.5 A
5.5 A
8.0 A
8.0A
Min. braking resistor
110
110
68
68
Recommended braking
resistor
Section 2.3
200
200
200
200
Ω
Motor-mounting (ventilated), or wall mounting with SK TIE4-WMK-L-1 (or -2) (ventilated)
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
2.2kW / 5.5A
3.0kW / 7.5A
3.0kW / 8.0A
4.0kW / 9.5A
4.0kW / 11.8A
5.5kW / 12.5A
5.5kW / 13.8A
7.5kW / 16.0A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
43°C
45°C
45°C
41°C
45°C
41°C
48°C
50°C
50°C
43°C
45°C
45°C
Wall mounting (unventilated)
Max. continuous power / max. continuous current:
S1-50°C
S1-40°C
S1-30°C
1.1kW / 3.1A
1.5kW / 4.0A
1.5kW / 4.8A
1.5kW / 4.0A
1.5kW / 4.9A
2.2kW / 5.7A
1.5kW / 5.3A
2.2kW / 6.9A
3.0kW / 8.4A
2.2kW / 6.3A
3.0kW / 7.9A
4.0kW / 9.4A
Max. permissible ambient temp. with nominal output current
S1
S3
70%ED 10min
S6
70%ED 10min (100% / 20%Mn)
-3°C
0°C
0°C
-20°C
-5°C
-15°C
1°C
15°C
5°C
-18°C
-5°C
-10°C
* Circuit Breaker (inverse time trip type) as per UL489
** FLA (S1-40 °C)