Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
P528
Load control delay
(Load monitoring delay))
S
P
0.1 ... 320.0 s
{ 2.0 }
From Firmware V1.3
Parameter (P528) defines the delay time for which an error message ("E12.5") is suppressed
on infringement of the defined monitoring range ((P525) … (P527)). A warning ("C12.5") is
triggered after half of this time has elapsed.
According to the selected monitoring mode (P529) an error message can also be generally
suppressed.
P529
Mode Load control
(Load monitoring mode)
S
P
0 ... 3
{ 0 }
From Firmware V1.3
The reaction of the frequency inverter to an infringement of the defined monitoring range
((P525) … (P527)) after the elapse of the delay time (P528) is specified by parameter (P529).
0 = Fault and warning, After the elapse of the time defined in (P528), an infringement of
the monitoring range produces a fault ""E12.5"). A warning ("C12.5") is given after the
elapse of half of this time.
1 = Warning only, After the elapse of half of the time defined in (P528) and infringement of
the monitoring range produces a warning ("C12.5").
2 = F a Warn during const, "Error and warning in constant travel", as for setting "0",
however monitoring is inactive during acceleration phases.
3 = Warning only
during
const, "Warning only during constant travel"
, as for setting 1, “,
however, monitoring is inactive during acceleration phases.