Parameter management
Parameter
Setting value / Description / Note
P1201
Copy - Source
Selection of the actual source object to be copied.
In the selection list, only the frequency inverters and storage media detected during the bus
scan are shown.
Value range: FI, S1 ... S5
P1202
Copy - Target
Selection of actual target object to copy.
In the selection list, only the frequency inverters and storage media detected during the bus
scan are shown.
Value range: FI, S1 ... S5
P1203
Copy - Start
This parameter triggers a transfer process, whereby all the parameters selected in >Copy
–
Source< are transferred to the object specified in the >Copy
– Target< parameter.
While data is being overwritten, an information window with acknowledgement appears .
The transfer starts after acknowledgement.
P1204
Load default values
In this parameter, the default settings are written to the parameters of the selected item.
This function is particularly important when editing storage objects. It is only via this
parameter that a hypothetical frequency inverter can be loaded and edited with the
ParameterBox.
Value range: FI, S1 ... S5
P1205
Delete memory
In this parameter the data in the selected storage medium is deleted.
Value range: S1 ... S5
Options
Parameter
Setting value / Description / Note
P1301
Language
Selection of languages for operation of the ParameterBox
Available languages:
German
English
Dutch
French
Spanish
Swedish
Polish
Italian
6
Danish
4
Finnish
4
Czech
4
Russian
4
P1302
Operating mode
Selection of the operating mode for the ParameterBox
Offline:
The ParameterBox is operated autonomously. The inverter data set is not accessed. The
storage objects of the ParameterBox can be parameterised and managed.
Online:
A frequency inverter is located at the interface of the ParameterBox. The frequency inverter
can be parameterised and controlled. On switchover to the "ONLINE “ mode, a bus scan is
automatically started. The FI parameters are not yet loaded.
PC Slave:
For connection to a PC with NORDCON software installed.
P1303
Automatic bus scan
Setting the switch-on characteristics.
Off:
A bus scan is not carried out, the frequency inverters connected before the switch-off are
located after switching on.
On:
A bus scan is automatically implemented when the ParameterBox is switched on.
P1304
Contrast
Contrast setting of the ParameterBox display
Value range: 0% ... 100%; Resolution 1%
6