NORD Drivesystems BU0200 User Manual
Page 295
SK 200E Manual for frequency inverters
294
Subject to technical alterations
BU 0200 GB-4411
b) 400V frequency inverter
For 50Hz operation, the motor can be used at the rated torque up to its rating point of 50Hz/400V. In spite of
this, operation above 50Hz is possible, however the output torque reduces in a non-linear manner (see
following diagram). Above the rating point the motor enters its field reduction range, as with an increase of
frequency above 50Hz, the voltage can not be increased above 400V. Due to the mains voltage, only max.
400V are available.
Up to a power of 2.2W, the following data refer to a 230/400V motor winding. Above 3kW the data is based
in 400/690V windings.
Frequency inverter type
Parameterisation data for frequency inverter
F
N
[Hz]
n
N
[min
-1
]
I
N
[A]
U
N
[V]
P
N
[kW] cos
Circuit
R
St
[
]
SK…80S/4 TI 4 - SK 2xxE-550-340-A
50
1375
1,52
400
0,55
0,73
Star
15,10
SK…80L/4 TI 4 - SK 2xxE-750-340-A
50
1375
2,10
400
0,75
0,74
Star
10,20
SK…90S/4 TI 4 - SK 2xxE-111-340-A
50
1385
2,78
400
1,1
0,78
Star
6,28
SK…90L/4 TI 4 - SK 2xxE-151-340-A
50
1385
3,64
400
1,5
0,80
Star
4,37
SK…100L/4 TI 4 - SK 2xxE-221-340-A
50
1440
5,22
400
2,2
0,74
Star
2,43
SK…100LA/4 TI 4 - SK 2xxE-301-340-A
50
1410
6,9
400
3,0
0,8
Delta
5,45
SK…112M/4 TI 4 - SK 2xxE-401-340-A
50
1445
8,3
400
4,0
0,8
Delta
3,44
SK…132S/4 TI 4 - SK 2xxE-551-340-A
50
1445
11,4
400
5,5
0,81
Delta
2,27
SK…132M/4 TI 4 - SK 2xxE-751-340-A
50
1445
14,8
400
7,5
0,84
Delta
1,45
Frequency inverter type
Power data at rating point
P
B
[kW]
n
B
[minP
-1P
]
M
B
[Nm]
SK…80S/4 TI 4 - SK 2xxE-550-340-A
0,55
1375
3,82
SK
…80L/4 TI 4 - SK 2xxE-750-340-A
0,75
1375
5,21
SK…90S/4 TI 4 - SK 2xxE-111-340-A
1,1
1385
7,58
SK…90L/4 TI 4 - SK 2xxE-151-340-A
1,5
1385
10,34
SK…100L/4 TI 4 - SK 2xxE-221-340-A
2,2
1440
14,59
SK…100LA/4 TI 4 - SK 2xxE-301-340-A
3,0
1410
20,32
SK…112M/4 TI 4 - SK 2xxE-401-340-A
4,0
1445
26,44
SK…132S/4 TI 4 - SK 2xxE-551-340-A
5,5
1445
36,5
SK…132M/4 TI 4 - SK 2xxE-751-340-A
7,5
1445
49,6