5 Commissioning

BU 0200 GB-4411

Subject to technical alterations

151

Internal view of SK 2xxE

Plug-in

EEPROM

8

-pi

n

DIP

swi

tc

h

5.2.2.2

DIP switch configuration Inverter (S1)

The DIP switches provide the possibility of carrying out commissioning without additional control units.
Further settings are made using the potentiometer on the top of the frequency inverter (P1 / P2, SK 2x5E
only).

As supplied, all DIP switches are at the "0" (Off) position, which corresponds to control via the digital inputs.
The frequency setpoint is changed with P1 and P2 (P1 / P2, SK 2x5E only).

NOTE

FACTORY SETTING, AS DELIVERED!

*) As delivered, all DIP switches are in the "0" ("off") position. Control is by means of the digital
control signals (P420 [01]-[04]) and the potentiometers P1 and P2 integrated in the FI
(P400 [01]-[02]) (P1 / P2 only SK 2x5E).

NOTE

For controlling the frequency inverter via In/Out bits (e.g.: AS-i, DIG In 1 - 4) typical values are
preset in the relevant parameters (P480) and (P481). (Details: Section 6)

These settings apply to both control via AS-i bits and BUS I/O bits.

No.

Bit

DIP switch (S1)

8

2

7

Int R

Brake

Internal brake
resistor

0

Behaviour corresponding to P555, P556, P557

I

The characteristics correspond to those of the brake
resistor recommended in Section 2.3.4

7

2

6

60Hz*

50/60Hz-operation

0

Motor data corresponding to the rated power of the
FI in kW relative to 50Hz, fmax = 50Hz

I

Motor data corresponding to the rated power of the
FI in hp relative to 60Hz, fmax = 60Hz

6

2

5

V/F

Regulating process

0

VFC regulation corresponding to P211/P212

I

V/f curve (

P211=0 and P212=0)

5/4

2

4/3

I/O

Potentiometer
function, digital
inputs and AS
interface

DIP-No

5

4

0

0

Corresponding to P420 [1-4] and P400 [1-2]
or P480 [1-4] and P481 [1-4]

0

I

Further

details

in

the

next

table.

(depends on the DIP3 "BUS")

I

0

I

I

3

2

2

BUS

Source control word
and setpoint value

0

Corresponding to P509 and P510 [1] [2]

I

System bus (

P509=4 and P510=4)

2/1

2

1/0

ADR

System bus
address/ baud rate

DIP-No

2

1

0

0

Corresponding to P514 and 515 [32, 250kBaud]

0

I

Address 34, 250kBaud

I

0

Address 36, 250kBaud

I

I

Address 38, 250kBaud

*) A changed setting is applied the next time the mains is switched on.
Existing settings in parameters P201-P209 and P105 are overwritten!