NORD Drivesystems BU0200 User Manual
Page 269
SK 200E Manual for frequency inverters
268
Subject to technical alterations
BU 0200 GB-4411
Display in the
SimpleBox
Warning
Text in the Parameter Box
Cause
Remedy
Group
Details in
P700 [-02]
C004
4.1
Overcurrent measurem
"Overcurrent from overcurrent
measurement"
Warning: Pulse switch-off is active
The limiting value for the activation of the pulse switch-off
(P537) has been reached (only possible if P112 and P536
are switched off)
FI is overloaded
Check motor data (P201 … P209)
C012
12.1
Limit moto /Customer
"Motor switch-off limit"
Warning: 80% of the drive switch-off limit (P534 [-01]) has
been exceeded.
Reduce load on motor.
Set a higher value in (P534 [-01]).
12.2
Limit gen
"Generator switch-off limit"
Warning: 80% of the generator switch-off limit (P534 [-02])
has been exceeded.
Reduce load on motor.
Set a higher value in (P534 [-02]).
12.3
Torque limit
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 12
12.4
Current limit
Warning: 80% of the limit from the potentiometer or the
setpoint source has been reached. P400 = 14
12.5
Load limit
Warning due to overshooting or undershooting of
permissible load torques ((P525) … (P529)) for the time set
in (P528).
Adjust load.
Change limit values ((P525) ... (P527)).
Increase delay time (P528).