Parameter
{Factory setting}
Setting value / Description / Note
Device
Supervisor
Parameter
set
Standardisation to typical signals, such as 0(2)-10V or 0(4)-20mA is carried out via the DIP
switch on the I/O extension module. In this case, additional adjustment of parameters (P402)
and (P403) must not be carried out.
P400 ... P403
Output
frequency
P104
z.B. 0,0 V 2,5 V 5,0 V 10,0 V
P105
positive
P402
P403
Setpoint
voltage
Output
frequency
P104
z.B. 0,0 V 2,5 V 5,0 V 10,0 V
P105
positive
negative
P402
P403
Setpoint
voltage
P404
[-01]
[-02]
Analog input filter
(Analog input filter)
SK 2x0E
1 ... 400 ms
{ all 100 }
Adjustable digital low-pass filter for the analog signal. Interference peaks are hidden, the
reaction time is extended.
[-01] =
Analog input 1
[-02] =
Analog input 2
P410
Min. freq. a-in 1/2
(Minimum frequency a-in 1/2
(auxiliary setpoint value))
P
-400.0 ... 400.0 Hz
{ 0.0 }
The minimum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies which are additionally supplied for further functions in the
FI:
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
PI process controller
PI controller
Multiplication
P411
Max. freq. a-in 1/2
(Maximum frequency a-in 1/2
(auxiliary setpoint value))
P
-400.0 ... 400.0 Hz
{ 50.0 }
The maximum frequency that can act on the setpoint via the auxiliary setpoints.
Auxiliary setpoints are all frequencies which are additionally delivered for further functions in the
FI:
Frequency addition
Frequency subtraction
Auxiliary setpoints via BUS
PI process controller
PI controller
Multiplication