2 configuration, 1 parameterisation – NORD Drivesystems BU0200 User Manual

Page 151

background image

SK 200E Manual for frequency inverters

150

Subject to technical alterations

BU 0200 GB-4411

5.2.2

Configuration

Changes to individual parameters are usually necessary for operation.

However configuration can be carried out to a limited extent with the by means of the integrated 8-pole DIP
switch (S1).

NOTE

Mixing of DIP switch configuration and (software) parameterisation should be avoided.

5.2.2.1

Parameterisation

The use of a ParameterBox (SK CSX-3H / SK PAR) or NORD CON software is necessary to change the
parameters.

Parameter group

Parameter numbers

Functions

Comments

Motor data

P201 … P207, (P208) Data on motor name plate

P220, Function 1

Measure stator resistance

Value is written to P208

alternatively

P200

Motor data list

Selection of a 4-pole standard
motor from a list

alternatively

P220, Function 2

Motor identification

Complete measurement of a
connected motor

Prerequisite: motor at least 3
power levels less than the
frequency inverter

Basic parameters

P102 … P105

Ramp times and frequency
limits

Control terminals

P400, P420

Analog and digital inputs

NOTE

Prior to commissioning, it should be ensured that the frequency inverter is in its default setting
(P523).

If configuration is carried out at the parameter level, the DIP switches (S1) must also be set to
the "0" (OFF) position.