2 configuration, 1 parameterisation – NORD Drivesystems BU0200 User Manual
Page 151
SK 200E Manual for frequency inverters
150
Subject to technical alterations
BU 0200 GB-4411
5.2.2
Configuration
Changes to individual parameters are usually necessary for operation.
However configuration can be carried out to a limited extent with the by means of the integrated 8-pole DIP
switch (S1).
NOTE
Mixing of DIP switch configuration and (software) parameterisation should be avoided.
5.2.2.1
Parameterisation
The use of a ParameterBox (SK CSX-3H / SK PAR) or NORD CON software is necessary to change the
parameters.
Parameter group
Parameter numbers
Functions
Comments
Motor data
P201 … P207, (P208) Data on motor name plate
P220, Function 1
Measure stator resistance
Value is written to P208
alternatively
P200
Motor data list
Selection of a 4-pole standard
motor from a list
alternatively
P220, Function 2
Motor identification
Complete measurement of a
connected motor
Prerequisite: motor at least 3
power levels less than the
frequency inverter
Basic parameters
P102 … P105
Ramp times and frequency
limits
Control terminals
P400, P420
Analog and digital inputs
NOTE
Prior to commissioning, it should be ensured that the frequency inverter is in its default setting
(P523).
If configuration is carried out at the parameter level, the DIP switches (S1) must also be set to
the "0" (OFF) position.