In order to implement completely autonomous operation (i.e. independent of control cables etc.) a
potentiometer unit (SK CU4-POT) is required. In combination with an integrated mains unit
(SK CU4-
…-24V) a solution can be implemented with an SK 2x5E which uses only one mains cable
(1~ / 3~ according to the version), and a suitable speed and direction control can be ensured (See
connection example below).
Connection plan and parameterisation of SK CU4-POT, example
Frequency inverter
SK 2x5E-...
Con
tro
l
te
rm
in
a
l b
a
r
44
40
.
.
21
22
23
24
.
.
.
SK CU4-POT
Potentio-
meter
0-10
R/0/L
Switch
L1 - L2/N - L3
115/230/400V
24V Mains unit
SK CU4-24V-...
L1 - L2/N
115/230/400V
24V=
GND
10V=
AGND
0-10V
R
L
0-100%
1/3~ 115/230/400V + PE
Control terminal bar
44 40 44 ... 11 14 12 B1
(br)
(bl)
(br)
(bk)
(wh)
(br)
(wh)
(bl)
DIP switch settings (S1:):
DIP3 = off, DIP4 = on, DIP5 = off
or
recommended
parameter setting, S1: DIP1-8 = off:
P400 [07] = 1 P420 [02] = 2
P420 [01] = 1 P420 [03] = 26
NOTE
An 8-Bit A/D converter is integrated into mains units SK TU4-
…-24V and SK CU4-…-24V. This
makes it possible to connect a potentiometer or other analog setpoint source to the mains unit
and to transfer this to the digital input of the frequency inverter via a corresponding pulse signal.