Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P741
[-01]
...
[-10]
PZD bus out
(Process data bus out)
S
0000 ... FFFF
(hex)
This parameter provides information about the actual status word and the actual values that are
transferred via the bus systems.
For standardisation of actual values: See also (Section 9.10).
[-01] = Status word
Status word
[-02] = Actual value 1 (P543 [-01])
[-03] = Actual value 2 (P543 [-02])
[-04] = Actual value 3 (P543 [-03])
[-05] = Res status Out Bit P481
"Resulting status of Out Bit P481"
The displayed value depicts all Bus Out
Bit sources linked with OR.
[-06] = Parameter data Out 1
[-07] = Parameter data Out 2
[-08] = Parameter data Out 3
[-09] = Parameter data Out 4
[-10] = Parameter data Out 5
Data during parameter transfer.
P742
Data base version
(Database version)
S
0 ... 9999
Displays the internal database version of the FI.
P743
Inverter ID
(Inverter type)
0.25 ... 11.00
Displays the inverter power in kW, e.g. "1.50"
FI with 1.5 kW nominal power.
P744
Configuration
(Configuration level)
0000 ... FFFF
(hex)
This parameter displays the special devices integrated in the FI. Display is in hexadecimal code
(SimpleBox, Bus system).
The display is in plain text when the ParameterBox is used.
High byte:
Low byte:
00
hex
01
hex
02
hex
03
hex
No extension
Encoder
Posicon
---
00
hex
01
hex
02
hex
03
hex
04
hex
05
hex
06
hex
07
hex
Standard I/O
(SK 205E)
STO
(SK 215E)
AS-I
(SK 225E)
STO and AS-I
(SK 235E)
Standard I/O
(SK 200E)
STO
(SK 210E)
AS-i
(SK 220E)
STO and AS-i
(SK 230E)
P747
Inverter Volt. Range
(Inverter voltage range)
0 ... 2
Indicates the mains voltage range for which this device is specified.
0 = 100...120V
1 = 200...240V
2 = 380...480V