5 Commissioning
BU 0200 GB-4411
Subject to technical alterations
153
5.2.2.3
DIP switch configuration, analog input (only SK 2x0E)
The analog inputs in the SK 2x0E are suitable for current and voltage set-
points. For correct processing of current setpoints (0-20mA / 4-20mA) the
relevant DIP switch must be set for current signals ("ON").
Adjustment (to fail-safe signals in case of cable breaks (2-10V / 4-20mA) is
made via parameters (P402) and (P403).
Access to DIP switches
SK 2x0E
Access
Detail
S 1 … 3
… from outside, middle
diagnostic opening
Size 4
... from inside
Similar to illustration
See also other documents in the category NORD Drivesystems For the car:
- B1000 (820 pages)
- B2000 (60 pages)
- B1050 (36 pages)
- B2050 (48 pages)
- B1091 (28 pages)
- B1091-1 (28 pages)
- B1092 (52 pages)
- B1901 (6 pages)
- B1904 (23 pages)
- BU0180 (184 pages)
- BU0210 (60 pages)
- BU0220 (100 pages)
- BU0230 (76 pages)
- BU0240 (40 pages)
- BU0260 (116 pages)
- BU0270 (76 pages)
- BU0280 (78 pages)
- BU0290 (76 pages)
- BU0300 (148 pages)
- BU0310 (8 pages)
- BU0320 (2 pages)
- BU0500 (180 pages)
- BU0505 (188 pages)
- BU0510 (81 pages)
- BU0530 (56 pages)
- BU0540 (64 pages)
- BU0550 (100 pages)
- BU0560 (4 pages)
- BU0570 (44 pages)
- BU0590 (48 pages)
- BU0700 (131 pages)
- BU0701 (1 page)
- BU0710 (32 pages)
- BU0750 (157 pages)
- BU0930 (8 pages)
- BU0940 (44 pages)
- BU2100 (34 pages)
- BU2200 (42 pages)
- MI0300 (36 pages)
- MI0700 (84 pages)
- BU0000 (85 pages)
- BU0010 (4 pages)
- BU0020 (104 pages)
- BU0040 (60 pages)