NORD Drivesystems BU0200 User Manual
Page 233
SK 200E Manual for frequency inverters
232
Subject to technical alterations
BU 0200 GB-4411
Parameter
Setting value / Description / Note
Device
Supervisor
Parameter
set
P715
Running time
(Enablement time)
0.00 ... ___ h
This parameter shows the time for which the FI was enabled and supplied current to the output.
P716
Current frequency
(Actual frequency)
-400.0 ... 400.0 Hz
Displays the actual output frequency.
P717
Current speed
(Actual rotation speed)
-9999 ... 9999 rpm
Displays the actual motor speed calculated by the FI.
P718
[-01]
...
[-03]
Current set freq.
(Actual setpoint frequency)
-400.0 ... 400.0 Hz
Displays the frequency specified by the setpoint.
[-01] = Actual setpoint frequency from the setpoint source
[-02] = Actual setpoint frequency after processing in the FI status machine
[-03] = Actual setpoint frequency after the frequency ramp
P719
Actual current
(Actual current)
0.0 ... 999.9 A
Displays the actual output current.
P720
Act. torque current
(Actual torque current)
-999.9 ... 999.9 A
Displays the actual calculated torque-developing output current (active current). Basis for
calculation is the motor data P201...P209 ... .
negative values = generator, positive values = drive
P721
Actual field current
(Actual field current)
-999.9 ... 999.9 A
Displays the actual calculated field current (reactive current). Basis for calculation is the motor
data P201...P209 ... .
P722
Current voltage
(Actual voltage)
0 ... 500 V
Displays the actual AC voltage supplied by the FI output.
P723
Voltage -d
(Actual voltage component Ud)
0 ... 500 V
Displays the actual field voltage component.
P724
Voltage -q
(Actual voltage component Uq)
0 ... 500 V
Displays the actual torque voltage component.
P725
Current cos phi
(Actual cos
)
0.00 ... 1.00
Displays the actual calculated cos
of the drive.
P726
Apparent power
(Apparent power)
0.00 ... 99.99 kVA
Displays the actual calculated apparent power. Basis for calculation is the motor data
P201...P209 ... .