However, in this case it should be noted that there is an increased risk of introducing interference into the
bus cables.
Connection of up to 8 sensors and 2 actuators is made via the terminal bar.
Digital inputs
System bus level and digital inputs
Digital outputs
24V
DIN 5
DIN 6
0V
24V
(as 1)
24V
(as 1)
24V
(as 1)
0V
0V
DIN 1
0V
24V
(as 1)
DIN 2
0V
24V
(as 1)
24V2
DO 1
0V 2
1
3
5
7
9
11
13
15
17
19
21
23
25
27
29
31
33
35
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
24V
(as 1)
DIN 7
DIN 8
0V
24V
(as 1)
24V
(as 1)
Sys +
Sys -
0V
DIN 3
0V
24V
(as 1)
DIN 4
0V
24V
(as 1)
0V2
DO 2
0V 2
Connection example: SK TU4-ECT to SK 205E
NOTE
Looping of the 24V supply voltage is possible, however a maximum current load of 3A for
the SK TU4-ECT(-
…) must not be exceeded.
Only adjacent terminals (e.g.: 11/12) may be used for looping.
Terminals 1/2 are preferentially for use with sensors and maximum loads of 500mA.
Potential level: system bus
Potential level: system bus
Potential level: DOs
Illustration of the terminal bar of the bus connection
unit SK TI4-TU-BUS with allocation of functions
S
K 205E… Adapter unit (SK TI4…)
SK TU4-
ECT… Adapter unit (SK TI4-TU-BUS)
Voltage
Source
24V DC